I N P U T S – O U T P U T S
Section 4. Inputs – Outputs, onboard switches, push buttons, ter minals
Inputs;
 High Voltage AC inputs: Inputs SAF, CG, LCK1, LCK2, M1 and M3 are high voltage input terminals or
monitoring points and switch to 110VAC or 240VAC with respect to M4/N
 Low Voltage DC inputs: Theses inputs switch low to 0 Volts with respect to 24VDC. The input shall draw
approximately 12mA. All inputs are OPTO isolated to avoid noise-related problems
Outputs;
 Transistor outputs: Outputs 1P-12, DDN, DUP, OS, HBS, switch high to 24V with respect to 0VDC
Transistor outputs can switch a maximum of 1.5A.
 Darlington outputs: These outputs switch low to 0V with respect to 24VDC
Darlington outputs can switch a maximum of 500mA and are OPTO isolated to avoid noise-related problems
Nb: For the 9 buttons below the LCD see Section 5 – LCD Control Buttons

BKS1 - BraKe Switch 1 input

BKS1 input turns on to indicate Brake 1 has lifted fully
Brake lift is monitored via a brake switch on the hoist machine, which inputs 0V to BKS1 input for Brake 1 when
fully lifted. If 2 brakes are used, BKS2 input monitors Brake 2. If only 1 brake used, connect brake switch to both
BKS1 and BKS2 inputs
Malfunctioning brake shall cause either of 2 fatal errors – BSD or BST. Reset is only via a processor POR.
BSD and BST errors shall be disabled when the lift is on inspection
BSD – BRK Drop Timeout error - When the brake does not drop 1 second from when lift stops.
Note: BSD error shall only set when the doors are closed to enable lift to re-level with the doors open
BST – BRK Lifting Timeout error – When the brake has not lifted after a run has been initiated
The door open button shall remain operative to allow passengers to exit the lift. Re-levelling is inhibited
BST error can be selected as an "immediate stop" or "stop next floor" error. See EEPROM settings, BST
See also LCD lift status BSD, BST
See also Inputs – Outputs BKS2
See also EEPROM setting BST, BSW

BKS2 - BraKe Switch 2 input

BKS2 input turns on to indicate Brake 2 has lifted fully. Operation as per BKS1
See also Inputs – Outputs BKS1

BRK - BRaKe relay output

Brake relay output contacts used to control the brake on traction jobs and the door lock valve on hydraulic jobs
See also Section 6: Motion, for more on the relay operation