I N P U T S – O U T P U T S

BSL - Bottom Slowing Limit input

Bottom floor position correction limit and forced slowdown limit for terminal floor
BSL input turns off as the lift approaches the bottom floor and activates the BSL limit switch
BSL input must remain off when lift is on the buffer
Ensure the MSD input turns on just before the Bottom Slowing Limit (BSL) at the bottom floor
See also Inputs – Outputs MSD

BYPASS onboard switch

Onboard lock BYPASS rotary selector switch
The BYPASS switch can be used to bypass the electrical safety contacts of either (only one at a time) the;
Car Gate – Switch in position CGBP. Doors must be closed (DFC input off)
Locks 1 – Switch in position L1BP
Locks 2 – Switch in position L2BP
When switched to a bypass position, the lift shall automatically be placed on inspection.
See also Inputs – Outputs BPAV, CGBP relay, L1BP relay, L2BP relay

BPAV - Bypass Switch Audio Visual alert output

Darlington Output
BPAV output turns on when the Lock BYPASS switch on the board is switched to CGBP, L1BP or L2BP
Used for driving an external relay, to control an audible signal at the car and a flashing light under the car

CFS - Car Fire Service input

CFS turns on when the lift is keyed to CFS, unless inverted with MOD setting
"Car Fire Service" shall be shown on the LCD screen
CFS allows only one car call to be entered at a time and shall toggle to the most recent call
When the doors are closed the lift shall run to the car call selected and stop with the doors closed
To open the doors on CFS, DOB input must turn off, and remain off, until the doors are fully closed
To close the doors on CFS, CFSS input must turn on, and remain on, until the doors are fully closed
CFS over rides hall fire service and independent service
See also Inputs – Outputs CFSS, DOB, HFS

CFSS - Car Fire Service Start input

CFSS input turns on when the door close button is pressed
CFSS input turns on to close the doors on Car Fire Service
To close the doors, CFSS input must turn on, and remain on, until the doors are fully closed
DOB and EDP shall be ignored when doors are closing on CFS
See also Inputs – Outputs CFS, DCB
CG – Car Gate input
High Voltage AC input
CG input turns on when the Car Gate contacts are made
CG input turns on CG LED
CG input pulls up CG relay
See also Inputs – Outputs CG Relay
CG relay – Car Gate relay
Onboard Relay Output
CG relay pulls up when CG input turns on
CG internal safety circuit relay contacts are monitored by CGM input
CG external relay contacts (CG - C, NO, NC) are used to provide the doors open signal to other devices (eg. voice
board TRIG input)
31