LCD Fault Log

From the Log Run/Doors Ops screen, press the Up button 3 times to reach the Fault Log
There are 10 faults recorded, with F01 being the most recent and F10 the oldest fault recorded
As a new fault is recorded at F01, the oldest fault at F10 shall be deleted
01-
NOR IDL
01-
NOR LCK-bad
Fault Runs:
00003228
Press the Up button to display older recorded faults
01-
NOR IDL
03-
OIL LCK
Fault Runs:
00002928
Press the Up button to reach the next 8 recorded faults, until the "Clear fault log" screen appears.
Press the Enter button to reset/clear the fault log. All faults shall be cleared from the fault log
Nb: To disable the "Clear fault log" function the COD and LCK EEprom parameters can be adjusted
01-
NOR IDL
Clear fault log..ENT
List of logged faults. See LCD modes/status for definitions;
 BCG
 BL1
 BL2
 BSD
 BST
 CG
 CGC
 CGO
 DCP
 DOP
 EQK
 L1C
 L1O
 L2C
 L2O
 LCK
 NPT
 OIL
][
F01
The LCD shown displays the most recent recorded fault (F01), as a
door lock fault (LCK-bad) on level 01 on run # 3228
][
[]
F02
The LCD shown displays the 2nd most recent fault (F02) as an
oil overheat fault (OIL) on level 03 on run # 2928
][