E E P R O M S E T T I N G S

Introduction

1.2.16
The 100-194 lift controller is a 12 stop, simplex or duplex (up to 6 car group), fully collective controller that has been
manufactured to comply with the EN81-20/50 standard.
Processor
Under normal operation;
 The red Red3 LED blinks to confirm that the microprocessor is running.
 The yellow Yel3 LED comes on to confirm outputs are enabled.
 The green Grn3 LED comes on during power up and turns off during normal operation. It will
When re-powering; ensure the lift is off for 10 seconds before turning back on.
On power up, a delay of approximately 2 seconds is given on start up to ensure voltages are stable prior to reading
and writing outputs.

Testing RCD / RCBO on 110vac Safety circuit.

To test the trip operation of an RCD / RCBO supplied with a 110VAC safety circuit, place a 1.2K ohm resistor
between the load side of the RCD / RCBO and earth.