Sf1 - Short Floor 1 Setup; Stf - Start Fast; Stm - Start Medium; Slf - Slow Fast - ECD 100-194 EN81 Manual

Table of Contents

Advertisement

E E P R O M S E T T I N G S

SF1 - Short Floor 1 setup

Note: this setting only works on MSL 00
Extension of SFR
This signal sets the short floor between 2 levels, so the controller will not set the fast speed relays (UF & DF).
SF1...EEPROM Must be FF: 11111111 unless stated.
A setting for a short floor between levels 10 & 11 would be as follows.
9,10,11,12,0000
1 0 0 1 1111. 10011111=AF
StF – Start Fast
Number of pulses (in hex) it takes to reach fast speed
Eg. 30: 00110000 (30 pulses in hex or 48 in decimal)
See also Section 6: Motion – EEPROM MSL setting "01", "02" & "03"
StM – Start Medium
Number of pulses (in hex) it takes to reach medium speed.
Eg. 20: 00100000 (20 pulses in hex or 32 in decimal)
See also Section 6: Motion – EEPROM MSL setting "01", "02" & "03"
SlF – Slow Fast
Number of pulses (in hex) it takes to slow from fast speed.
Eg. 30: 00110000 (30 pulses in hex or 48 in decimal)
See also Section 6: Motion – EEPROM MSL setting "01", "02" & "03"
SlM – Slow Medium
Number of pulses (in hex) it takes to slow from medium speed.
Eg. 20: 00100000 (20 pulses in hex or 32 in decimal)
See also Section 6: Motion – EEPROM MSL setting "01", "02" & "03"
SSD – Soft Start Drive
Hydraulic lifts only. V6.04 software onwards.
Set SSD to 01: 00000001 when hydraulic lift with Soft Starter motor starting
When SSD = 01, SP2 relay operates as per UP relay. SP2 C and N/O contacts are used to issue the run command
to the Soft Starter. This ensures 2 forms of motor disconnection.
FF: 11111111 (Hydraulic lift with Star Delta motor starting)

ST2 - STar delta 2 setup

Star connected motor running time.
The amount of time the motor runs in Star, before changing to Delta.
The time is set in 100ms increments.
08: 00001000 = 800ms
0a: 00001010 = 1000ms, "1 second"
12: 00010010 = 1800ms, "1.8 seconds"
ST2 – VF Drive setting 06,07,08 end run time
Valid only when EEPROM setting "DRV" is set to "06, 07, 08".
This sets the amount of time after a run for the Up/Dn relays to drop in 10ms increments.
Set between 01 & ff .
ST2 value must be greater than SDX value

TCC - Top Car Call setup

The controller shall enter a car call to this setting when the "TOP CALL' button on the circuit board is pressed
23