E E P R O M S E T T I N G S
FD1 – Front Doors 1 setup, levels 1-8
This sets the levels for the front doors to operate on levels 1-8
May be used in conjunction with RD1 and SD1 for selective rear door operation
FD1 A0: 10100000 (Level G and level 2 have front doors)
RD1 50: 01010000 (Level 1 and level 3 have rear doors)
FLOOR DESIG.
3
2
1
G
See also EEPROM setting RD1, SD1
FD2 – Front Doors 2 setup, levels 9-12
This sets the levels for the front doors to operate on levels 9-12
Setting example: E0: 11100000 (Levels 9-11)
May be used in conjunction with RD2 and SD2 for selective rear door operation
See also EEPROM setting RD2, SD2

HFS - Hall Fire Service return floor setup

This sets the hall fire service return floor when HFS input turns on
80: 10000000 (Level 1)
40: 01000000 (Level 2)
20: 00100000 (Level 3)
10: 00010000 (Level 4)
08: 00001000 (Level 5)
04: 00000100 (Level 6)
02: 00000010 (Level 7)
01: 00000001 (Level 8)
See also Inputs-Outputs HFS
HF1 – Hall Fire 1 setup
Extension of HFS.
80: 10000000 (Level 9)
40: 01000000 (Level 10)
20: 00100000 (Level 11)
10: 00010000 (Level 12)
HRF – Hospital / Hall Recall Floor
This sets the Hospital /Hall Recall Floor when lift is in HR mode
See also Inputs-Outputs HRI
eg. 40: 01000000 (Level 2)
HR1 – Hospital / Hall Recall 1 setup
Extension of HRF
eg. 40: 01000000 (Level 10)
See also Inputs-Outputs HRF
LCK – Parameter lockout function
To stop unauthorised adjustments to the EEPROM parameters and to also disable the "Clear fault log" function
(see Section 5 – LCD Fault Log), the COD and LCK parameters are used
FRONT DOORS
2 (front) 3C, 3U, 3D
G (front) 1C, 1U
REAR DOORS
3 (rear) 4C, 4D
1 (rear) 2C, 2U, 2D
18