Section 7: Faults – Fault finding.
On board fuse blows
There are 2 fuses mounted on the controller board.
The 2A fuse protects the 5Vdc supply to all the logic on board.
The 4A fuse protects the 24Vdc supply.
If 2A (5Vdc) fuse blows check that the 6V Zener diode is not short circuited. (return for repairs)
If 4A (24Vdc) fuse blows.
Test for fault on 24Vdc circuits (inputs/outputs)
Remove all external plugs except 18Vac and 10Vac
Replace fuse. If 4A fuse still blows, check that the 30V Zener diode is not short circuited. (return for
repairs)
If fuse does not blow plug in external inputs/outputs one plug at a time and test for external fault.
Testing 24Vdc
Ensure 0V and +24V are free from other voltages.
Ensure 0V is not connected Earth.
High voltages may be superimposed on 0V and +24V lines as no reference to ground exists. See Warning 1.2.14
Turn the meter to the HIGH VAC range.
Meter between 0V and Neutral. (Should be 0V)
Meter between 0V and L2A (if applicable). (Should be 0V)
Meter between +24V and Neutral. (Should be 0V)
Meter between 0V and +24V. (Should be 24Vdc)
If 24Vdc is low or unstable, check large capacitor C69 on PCB. This capacitor may have been hit or knocked,
which can break off one of the legs soldered into the PCB. A gentle twist will reveal if one leg has broken. If so,
replace the capacitor
Testing RCD / RCBO on 110vac Safety circuit.
To test the trip operation of an RCD / RCBO supplied with a 110VAC safety circuit, place a 1.2K ohm resistor
between the load side of the RCD / RCBO and earth.
Doors do not open
Check door disable switch DDO on PCB is off
See Inputs-Outputs, DDO
Doors don't open at terminal floors
Ensure the MSU slowing input is activated before the Top Slowing Limit (TSL) at the top floor
Ensure the MSD slowing input is activated before the Bottom Slowing Limit (BSL) at the bottom floor
See prints for magnet and limit positions
76
Section