RPT - Run Protection Timer setup

If the lift is given run signals from controller and lift does not move, (no MSU or MSD input received) the
controller turns off all run signals after a certain time, (e.g. 25s) depending on value of the RPT setting. If this
process is cycled 3 times, then the controller shall display RPT error message on the LCD screen.
RPT is a fatal error. Reset is only via a processor POR or Inspection on/off sequence.
Setting example 01: 00000001 = 25s
02: 00000010 = 50s
03: 00000011 = 75s
All other remaining settings including 00, will default to the value of 25s.
RPT does not operate on inspection or on DRV setting "01" (DA valve).
RTM – Run Time short floor run setup
If a short floor exists where the lift starts slowing prior to reaching full speed, a long creep into floor may occur.
RTM setting, in conjunction with XTM setting, can reduce this long creep time by holding in the fast speed relay
for a defined (XTM) time after the initial slowing point.
Setting RTM. – Look at Ram address R:72. (Motion Timer).
When performing the shortest floor run take note of the highest value R:72 reaches (in hex). Add approx. 5 (in hex)
to this value and set RTM to this value.
If slowing is obtained before the value in RTM is reached, the fast speed relay (UF or DF) will be held up for extra
time as defined by XTM. See XTM setting.
RTM and XTM may be used as above for both MSL=00 and MSL=01 (pulse counting) settings.

SDX - Star Delta Exchange Time setup

This sets the amount of time from Star dropping out and Delta picking up.
SDX EEPROM Star Delta Exchange time. (VALUE)
Set value for delay between star dropping and delta pulling in.
The time is set in 100ms increments.
08: 00001000 = 800ms
Set between 01 & 08

SDX - VF Drive setting 06,07,08 brake drop time

Valid only when Eeprom setting "DRV" is set to "06, 07, 08".
This sets the amount of time after a run for the brake drop in 10ms increments.
SDX value must be less than ST2 value
Set between 01 & ff

SFR - Short Floor Run setup

Note: this setting only works on MSL 00
This signal sets a short floor between floors, i.e the controller will not set the fast speed relays (UF & DF).
SFR...EEPROM Must be FF: 11111111 unless stated.
A setting for a short floor between levels 2 & 3 would be as follows.
12345678
10011111
02-
NOR IDL
R:70
00 OA
00
To access R:72 on the LCD see also Section 5: LCD
][
Display Options
14
R: 72 shown in red at left.