On Delay Block; Counter Block - Siemens SIDOOR ATD4 W Series System Manual

Automatic door control units
Table of Contents

Advertisement

SIDOOR functions
4.3 Extended functions
Input signal
Output signal
The output signal changes after 3 detected signal periods after the 4th edge
An input tolerance of (±) 40 ms is assumed.
Duty cycle: 20 % (17 to 23 %)
1 Hz frequency detection:
– T = 1000 ms (±2 %)
– t
= 200 ms
on
– t
= 800 ms
off
– Pulse/pulse ratio V = 25 %
0.5 Hz frequency detection:
– T = 2000 ms (±2 %)
– t
= 400 ms
on
– t
= 1600 ms
off
– Pulse/pulse ratio V = 25 %
Figure 4-10
Frequency-based input signal detection
The outputs Q24 or Q26 become active when the analysis algorithm detects a frequency of 1 Hz
with a 20 % duty factor in the input signal. The outputs Q25 or Q27 become active when the
analysis algorithm detects a frequency of 0.5 Hz with a 20 % duty factor in the input signal.
The maximum response time at the output, i.e. the time after which the system can detect an
error or a deviation in the input signal frequency, corresponds to the period of the frequency to
be detected. Accordingly, a frequency of 1 Hz results in a maximum response time of 1 s and a
frequency of 0.5 Hz results in a maximum response time of 2 s.
4.3.9.9

On delay block

The "OnDELAY" block delays the input signal at the output Q28 by 2 s and at the output Q29 by
5 s.
4.3.9.10

Counter block

The "COUNTER" block increments the internal counter value in the event of a positive edge at the
input.
100
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA