Test Voltage - Siemens SIDOOR ATD4 W Series System Manual

Automatic door control units
Table of Contents

Advertisement

7.3.4

Test voltage

Figure 7-7
The type test and the manufacturing test can only be performed by the manufacturer. The field
can also be performed by the user.
Requirements for performing the field test:
General
Disconnecting SIDOOR TRANSFORMER UL
disconnect the connection to the SIDOOR control circuit device.
Inspection (A) & (B)
• Interconnecting input lines (PRI) L1 and L2/N
• Interconnecting output cables (SEC) VCC, GND and PE
Inspection (C)
• Interconnecting output cables (SEC) VCC and GND and measuring against PE
Table 7-2
Type test
Manufacturing test
Field test
Remark:
Tripping current for measuring DC: 0 mA
tripping current for measuring AC: <100 mA
ATD4xxW for industrial applications
System Manual, 06/2022, A5E51901827B AA
Diagram test voltage
Test voltage
Test time
PRI<->SEC (A)
60 s
4000 VAC
1 s
4000 VAC
1 s
1500 VAC
1 s
2250 VDC
7.3 SIDOOR TRANSFORMER UL
PRI<->PE (B)
SEC<->PE (C)
4000 VAC
1500 VAC
4000 VAC
1500 VAC
1500 VAC
350 VAC
2250 VDC
500 VDC
Power supply
255

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents