9.2 Transferring to Maintenance Bypass Mode

● You are advised to install a lock on the maintenance bypass switch.
● Strictly observe the following procedure to transfer the UPS to maintenance
● In maintenance bypass mode, the mains supplies power to the loads directly
Step 1 Ensure that the status signal cable of the maintenance bypass switch for external
power distribution is connected to MT/0V.
Figure 9-1 Maintenance bypass signal port (MT)
Step 2 Choose System Info > Settings > Dry Contact Set, set MUE05A connection to
Enable, and set PDC maintenance breaker [MT] to Enable.
Step 3 Shut down the inverter. Choose Common Functions > Inv. OFF. After the inverter
shuts down, the UPS transfers to bypass mode, and the Bypass mode alarm is
displayed on the LCD.
Step 4 Turn on the maintenance bypass switch for external power distribution. Then, the
PDC Maint. breaker closed and Bypass mode alarms are displayed on the LCD.
----End
Issue 07 (2022-11-29)
NO TICE
bypass mode. Otherwise, loads may power off.
over the maintenance bypass. If the mains is abnormal, the loads may power
off.