7.3.1.2 Performing a Shallow Discharge Test

This item allows you to partially discharge batteries. A shallow discharge test is
conducted to test the battery loop reliability and short-time discharge capacity
when the batteries have not been discharged for a long time.
Before performing a shallow discharge test, ensure that:
● If the battery has been replaced, choose System Info > Settings > Battery
● The UPS works in normal mode with a load rate fluctuation less than 10%.
● The UPS generates no battery overtemperature, overvoltage, or overcurrent
● The mains, batteries, charger, and discharger are normal. No overload alarm is
● If the UPS does not communicate with SmartLi 3.0, batteries are managed as
Issue 07 (2022-11-29)
NO TE
The forced equalized charging test automatically stops in any of the following cases:
● The test duration reaches the forced equalized charging protection time (12–24 h, 18 h
by default).
● The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
● An alarm is generated.
NO TICE
Settings on the LCD and verify that the value of Installation time has been
changed based on the actual situation before testing the battery.
alarm. No generator is connected to the UPS.
generated.
lead-acid batteries by default. Because the battery capacity is set to the
maximum value on the UPS UI, the battery capacity displayed on the
monitoring UI of the SmartLi should be used during a shallow discharge test.
Otherwise, batteries may be completely discharged.