Huawei UPS5000-H-800 Quick Manual

Advertisement

Quick Links

01
Installing Cabinets
1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only qualified professionals or trained personnel are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage
may occur, and the caused UPS damage is not covered under any warranty or service agreement.
4. This document describes the operation procedure for a single UPS. For details about how to operate a parallel system, see the user manual.
Unpacking
Space Planning
Inductor
cabinet
UPS
cabinet
Recommended Power Cables
Item
800 kVA
Mains input current (A)
1486
Mains input
Recommended cross-
L1/L2/L3
4 x (3 x 240)
sectional area (mm
2
)
PE
240
Bypass input current (A)
1215
Bypass input
Recommended cross-
L1/L2/L3
4 x (3 x 240)
sectional area (mm
)
2
PE
240
Output current (A)
1215
Output
Recommended cross-
U/V/W
4 x (3 x 240)
sectional area (mm
2
)
PE
240
Nominal battery discharge current (A)
1773
Battery input
Maximum battery discharge current (A) 2123
(lead-acid
Recommended cross-
+/-
4 x (2 x 240)
battery)
sectional area (mm
2
)
PE
240
Nominal battery discharge current (A)
1662
Maximum battery discharge current (A) 2086
For details, see
Battery input
the IEC-60364-
(SmartLi)
Recommended cross-sectional area
5-52
(mm
2
)
specifications
and SmartLi
User Manual.
Equipotential
Recommended cross-sectional area
16
ground point
(mm
2
)
Connection method: Crimped DT terminal
Bolt specifications: L1/L2/L3/U/V/W/+/-:M16 x 55 mm (120 N· m)
PE: M12 x 30 mm (47 N· m)
Equipotential ground point: M6 x 12 mm (4.5 N· m)
NOTE: The currents listed in the table are measured at a rated voltage
of 380 V.
UPS5000-H-800 kVA Quick Guide (100 kVA Power Modules, Three-Phase Three-Wire)
安装流程
UPS
cabinet
Inductor
cabinet
Cabinet Description
Power
modules
Bypass fan power
Bypass modules
supply unit (PSU)
Model
Weight
UPS5000-H-800K-NTN
< 1300 kg
Inductor cabinet
< 550 kg
Securing the Cabinets
UPS
unit: mm
A: mounting holes on the channel steel
B: mounting holes on the floor
Rectifiers
Fan power
switch QS1-4
Main switch QF
of the inductor
cabinet
Control module
Fans
1
Issue: 02
Date: 2022-12-29
Dimensions (H x W x D)
2000 mm x 1600 mm x 1000 mm
2000 mm x 400 mm x 1000 mm
Inductor cabinet
M12 bolt
Spring washer
Flat washer
Expansion
Concrete floor
sleeve
Expansion nut
Copyright © Huawei Digital Power Technologies Co., Ltd. 2022. All rights reserved.

Advertisement

loading

Summary of Contents for Huawei UPS5000-H-800

  • Page 1 Equipotential ground point: M6 x 12 mm (4.5 N· m) Bypass fan power NOTE: The currents listed in the table are measured at a rated voltage Bypass modules supply unit (PSU) of 380 V. Copyright © Huawei Digital Power Technologies Co., Ltd. 2022. All rights reserved.
  • Page 2 UPS5000-H-800 kVA Quick Guide (100 kVA Power Modules, Three-Phase Three-Wire) 安装流程 Installing Rectifiers and Cables Mains input output Battery input • Cables have been preinstalled and bound in the inductor cabinet. Signal cable route outside the cabinets • The cables from the inductor cabinet to the UPS are configured based on the longest cable length before delivery.
  • Page 3 UPS5000-H-800 kVA Quick Guide (100 kVA Power Modules, Three-Phase Three-Wire) Shutting Down the UPS Power-On Commissioning Shutting Down the Inverter to Transfer the UPS to Bypass Mode 1. Before powering on the UPS5000, ensure that the check items in the...