Huawei UPS5000-H-1200K-NT User Manual page 268

Hide thumbs Also See for UPS5000-H-1200K-NT:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Module)
Figure 4-269 Installing top supports and covers
Step 6 Install input and output busbars.
Table 4-13 Power cable terminal requirements
Port
Mains input/bypass
input/output/PE
Step 7 Install power distribution units. (If the mains input and bypass input share a
power source, a power distribution unit must be deployed for the copper bars that
are not installed in the busway. Copper bars must not be exposed.)
Step 8 (Perform this step only for the top air-flow configuration.) Install cables for the
top air-flow cabinet.
1.
2.
3.
Issue 07 (2022-11-29)
Remove the front cover from the UPS.
Remove an accessory cover from the top of the top air-flow cabinet.
Connect the power cable to the 380~480V System port on the UPS and the
signal cable to the XS2 port.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Connecti
Bolt
on
Specificati
Method
ons
Crimped
M12
DT
terminal
4 Installation and Cable Connection
Bolt Length
45 mm
Torque
47 N·m