Huawei UPS5000-H-1200K-NT User Manual page 105

Hide thumbs Also See for UPS5000-H-1200K-NT:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Module)
Figure 4-9 Battery copper bar wiring holes (1600K, unit: mm)
Issue 07 (2022-11-29)
The recommended cross-sectional areas of AC power cables in the table are
based on the default 380 V AC current and are compatible with 400 V AC and
415 V AC application scenarios. For details about the current values, see the
current parameters in the technical specifications.
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
The cables must be flame-retardant, and the flame spread rating of the
cables must meet the UL 1581 VW-1, IEC 60332-3-22 (ZB), or higher
requirements.
When selecting, connecting, and routing cables, follow local safety regulations
and rules.
When the external conditions such as cable routing or ambient temperature
change, perform verification in accordance with the IEC 60364-5-52 or local
regulations.
When lead-acid batteries are used, it is recommended that the battery cable
specifications be selected based on forty 12 V batteries by default and
compatible with application scenarios with 30–50 batteries.
When SmartLi batteries are used, it is recommended that the battery input
cable specifications be selected according to the IEC-60364-5-52 standard and
SmartLi user manual
When the mains input and bypass input share a power source, configure
mains input power cables as input power cables.
The cables listed in the tables are used only when the following requirements
are met:
Multi-core cables are recommended for the mains and bypass input and
output power cables, and single-core cables are recommended for the
battery cables.
Routing mode: Mains and bypass input and output power cables are
routed over a ladder or bracket (E in IEC 60364-5-52), and the distance
between cables is greater than twice the cable diameter. Battery cables
are routed over a ladder or bracket in a single layer (F in IEC
60364-5-52).
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
96

Advertisement

Table of Contents
loading

Table of Contents