Transferring From Maintenance Bypass Mode To Normal Mode; Performing Epo - Huawei UPS5000-E-FM User Manual

Hide thumbs Also See for UPS5000-E-FM:
Table of Contents

Advertisement

UPS5000-E-(30 kVA-120 kVA)-FM
User Manual
----End
8.3 Transferring from Maintenance Bypass Mode to
Normal Mode
Context
Before transferring the UPS from maintenance bypass mode to inverter mode,
ensure that the bypass input and output are normal.
Procedure
Step 1 Turn off the maintenance bypass switch.
The Maint. breaker closed alarm disappears from the alarm list. View the system
running diagram on the LCD or WebUI to check whether the system works in
bypass mode.
Step 2 Start UPS inverters.
----End

8.4 Performing EPO

● After the EPO button is turned on, the UPS supplies no power and the loads
● In maintenance bypass mode, the UPS continues to supply power even after
Press the external EPO switch that connects to the dry contact card or remove the
4-pin terminal on the EPO port of the dry contact card.
Issue 05 (2023-07-10)
NO TE
After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and
Bypass mode alarms are displayed on the LCD.
NO TICE
NO TE
If a lock, stopper, or barrier is configured for the maintenance bypass switch, lock the switch
or reinstall the stopper or barrier.
NO TICE
shut down.
the EPO button is turned on.
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 FAQ
147

Advertisement

Table of Contents
loading

Table of Contents