UPS5000-A-(400 kVA-500 kVA)
User Manual (40 kVA Power Modules)
Figure 5-32 Turning on the maintenance bypass switch (UPS in full configurations)
Figure 5-33 Maint. Breaker closed
----End
5.8 Transferring from Maintenance Bypass Mode to
Normal Mode
Prerequisites
Before you switch the system from maintenance bypass mode to normal mode, ensure that the
input and output of the system bypass are normal.
Issue 06 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
5 Operation Guide
169