UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Module)
Step 8 Install battery cables.
Figure 4-362 Installing battery cables
Step 9 (Perform this step only for the top air-flow configuration.) Install cables for the
top air-flow cabinet.
1.
2.
Issue 07 (2022-11-29)
If the mains input and bypass input share a power source, you do not need to
remove the copper bar between the mains and bypass input terminals or
connect the bypass input power cable.
NO TE
Battery cabinet connection requirements: If the UPS capacity is 800 kVA or lower, connect
battery cables only to the power cabinet on the left. If the UPS capacity exceeds 800 kVA,
connect battery cables equally to both power cabinets. If the number of battery cabinets is
an odd number, the remaining battery cabinet can be connected to any of the power
cabinets.
Remove an accessory cover from the top of the top air-flow cabinet.
Connect the power cable to the 380~480V System port on the UPS, connect
the signal cable of the top air-flow cabinet on the left to the PU XS2-1 in
power cabinet 1, and connect the signal cable of the top air-flow cabinet on
the right to the PU XS2-2 in power cabinet 2.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation and Cable Connection
315