Transferring From Maintenance Bypass Mode To Normal Mode - Huawei UPS5000-E-125 kVA User Manual

Hide thumbs Also See for UPS5000-E-125 kVA:
Table of Contents

Advertisement

UPS5000-E-125 kVA
User Manual (Integrated UPS 3.0, 02291136)
Procedure
Step 1 Manually transfer the UPS to bypass mode.
Step 2 Loosen the screws using a Phillips screwdriver, remove the baffle plate from the
maintenance bypass circuit breaker, and switch on the circuit breaker.
The Maint. breaker closed alarm is displayed in the alarm list on the LCD.
Figure 4-17 Maint. breaker closed alarm
----End
4.13 Transferring from Maintenance Bypass Mode to
Normal Mode
Context
Before you transfer the UPS from maintenance bypass mode to normal mode,
ensure that the bypass input and output are normal.
Procedure
Step 1 Turn off the maintenance bypass switch.
Press down the maintenance bypass switch to turn it off.
The Maint. Breaker closed alarm disappears from the alarm list. Check whether
the UPS works in bypass mode by viewing the system running diagram on the
LCD.
Issue 01 (2022-09-26)
NO TE
After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and
Bypass mode alarms are displayed on the MDU.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Operations
110

Advertisement

Table of Contents
loading

Table of Contents