Transferring From Maintenance Bypass Mode To Normal Mode - Huawei UPS5000-E User Manual

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Procedure
Step 1 Manually transfer the UPS to bypass mode.
Step 2 Loosen the screws using an insulated Phillips torque screwdriver, remove the baffle
plate from the maintenance bypass circuit breaker, and switch on the maintenance
bypass circuit breaker.
The Maint. breaker closed alarm is displayed in the alarm list on the LCD.
Figure 6-17 Maint. breaker closed alarm
----End
6.15 Transferring from Maintenance Bypass Mode to
Normal Mode
Context
Before you transfer the UPS from maintenance bypass mode to normal mode,
ensure that the bypass input and output are normal.
Procedure
Step 1 Turn off the maintenance bypass switch.
Press down the maintenance bypass switch to turn it off.
The Maint. Breaker closed alarm disappears from the alarm list. Check whether
the UPS works in bypass mode by viewing the system running diagram on the
LCD.
Issue 06 (2023-08-25)
NO TE
After the UPS transfers to maintenance bypass mode, the Maint. breaker closed and
Bypass mode alarms are displayed on the MDU.
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Power-On and Commissioning