UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Module)
2.7.4 Ambient T/H Sensor
●
●
Figure 2-32 Appearance
(1) RJ11 ports
Table 2-13 RJ11 port pin definitions
Appearance
2.7.5 PVC for Rear Copper Bar Protection
The material protects copper bars at the rear of the cabinet.
Issue 07 (2022-11-29)
The ambient T/H sensor monitors the ambient temperature and humidity in
the equipment room to ensure that the equipment works properly.
The ambient T/H sensor can also be used as a battery temperature sensor.
The monitoring module distinguishes these two types of sensors through their
DIP switch settings.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Pin
RJ11 Port
1
GND
2
-
3
S_RS485B_R–
4
S_RS485B_R+
5
-
6
12V_OUT
2 Product Overview
61