UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Module)
Parameter
SOC threshold to
exit peak shaving
(%)
Step 2 When Peak shaving rule configuration mode is set to Importing
Configurations, you can import a configuration file to configure peak shaving
rules. Multiple rules are supported.
1.
2.
Issue 07 (2022-11-29)
Description
When the battery SOC is less
than or equal to the preset
threshold, batteries enter the
non-charge and non-
discharge state during a
discharge period, and
batteries are charged
normally during a charge
period. When the battery
SOC is greater than the
preset threshold, the system
implements peak shaving
based on the preset rules.
NO TE
When the status of the system is lower than the setting of Normal backup time reserved
for peak shaving (min) or SOC threshold to exit peak shaving (%), batteries enter the
non-charge and non-discharge state during a discharge period, and batteries are charged
normally during a charge period. When the status of the system recovers to the settings,
the system continues to implement peak shaving based on the preset rules.
Obtain an electricity price template from the NetEco or technical support
engineers and configure the peak shaving settings.
a.
Choose EleConfig on the menu bar and set Select Product to Data
Center UPS
Figure 5-16 Electricity price template
b.
Select a mode and set basic parameters as prompted.
NO TE
If you select the month or week mode, you can click HolidayMod to set
holiday mode parameters on the corresponding tab page.
The parameter settings must meet the verification rules of the template.
Otherwise, a Bin file cannot be generated.
Save the electricity price template and generate a 2.0 Bin file.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
Default Value
Value Range
50
0–100
370