Downloading Configuration And Exporting Cid File - ABB SPA-ZC 400 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS755347
6.8.
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Fig. 6.7.1.-1
SPA Communication Parameters

Downloading configuration and exporting CID file

After you have built the IEC 61850 data model and done the communication
addressing, you can download the configuration to SPA-ZC 400:
1. Select the IEC 61850 Device object and right-click to select the CID
Export.
2. If you download configuration to SPA-ZC 400 the first time, change the IP
address from default address (192.168.2.10) to new IP address according
to the planned network structure.
When the new configuration to SPA-ZC 400 is downloaded, Communication
Engineering Tool (CET) checks if the basic IP addresses are changed. If a
change is detected, CET asks whether new addresses are taken into use. If the
changes are not accepted, SPA-ZC 400 uses the old IP address from the
previous configuration. The IP addresses can be verified with, for example, IP
Query Tool. For more information about IP Query Tool, refer to
Section 9.3. IP Query.
SPA-ZC 400
A040022
43

Advertisement

Table of Contents
loading

Table of Contents