Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Fig. 7.1.-1
Diagnostic counters seen on MicroSCADA Pro IEC 61850 client
The q attribute quality bits of the properly updated data objects
indicate GOOD or DEFAULTED. If this is not the case,
configurations between SPA-ZC 400 and REF 541/3/5,
REM 543/5 or RET 541/3/5 are not identical. If all the data
objects have INVALID quality, the SPA communication is not
running.