In order to get automatic updating of the process objects, you
should add those data objects of interest to the dataset group.
Refer to Section 6.5. Using Dataset Editor.

Configuring report control blocks

Report control block (RCB) controls the spontaneous event reporting. A
client can modify report sending behavior by setting RCB attributes. RCB
attributes have suitable default values for the following ABB products:
COM 610 and MicroSCADA Pro IEC 61850 client. RCBs are located under
the logical device LD0 and logical node LLN0.
Get, Set report
Control
control attribute values
Subscribe for reporting
controls
Reports
Handler*
* local issue
Fig. 6.10.-1
Reporting model
RCB's have the following properties. To edit the properties, right-click the
dataset and select Properties.
Buffered reporting
*
IEC 61850 buffers events also during the communication break.
Buffer Time
*
Default value for buffered reporting is 100 milliseconds (ms). With this
value, RCB waits 100 ms for other events after the first change before
sending the report.
Integrity Period
*
Default value for Integrity Period is 0 ms. If this attribute has value > 0
ms, SPA-ZC 400 sends a report with all data listed in linked data set with
this period. By default this feature is not enabled because it generates
unnecessary load to server and network.
Report ID
*
By default this attribute is empty and SPA-ZC 400 uses it for RCB MMS
address. If this string is left empty, a default report control block MMS
path name is used.
Report
has association
controls
Report
Event
event
Monitor*
SPA-ZC 400
Data
Set
DO
Data
Set
Real
DO
Data
DO
DO
DO
DO
DO
DO
DO
A060032