Adding Device Object; Adding Logical Device Objects - ABB SPA-ZC 400 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS755347
6.4.1.
6.4.2.
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
7. GOOSE control blocks
8. GOOSE inputs

Adding Device object

To build the object tree:
1. Add an IEC 61850 Device object in the communication structure by
selecting the project name.
In the example the project Protocol Test is selected.
2. Right-click Protocol Test
3. Select New > IEC 61850 > SPA-ZC 40x, see Fig. 6.4.1.-1.
A project can contain several IEC 61850 Device objects, for example all
substation feeder configurations and exported communication must be done
separately for each device.
Fig. 6.4.1.-1
Adding an IEC 61850 Device object
Ensure that the new IED name is unique within the planned network by
renaming the IED, for example REF545_F1.
A Tunneling Device object cannot be configured for an IEC
61850 gateway.

Adding Logical Device objects

Communication Engineering Tool (CET) creates logical device LD0
automatically for SPA-ZC400 when creating a new IED. All datasets and
reporting control blocks (RCB) are grouped under LD0 for event handling. It
has also basic logical nodes and data objects for diagnostics and device
information.
SPA-ZC 400
A040023B
35