When this parameter is enabled, SPA-ZC 40x uploads disturbance recording files
from the MEDREC function block to SPA-ZC 40x file system in COMTRADE
format. IEC 61850 client can get these files when it receives an event from the
RDRE logical node. This parameter is enabled by default and you should ensure
that your system has an IEC 61850 client that is capable to use the IEC 61850
File Transfer protocol. For example, CAP 505 and PCM600 use SPA over TCP
to upload the disturbance recording files. FTP is used by COM600 or RTU.
The parameter is valid with REF 541/3/5, REM 543/5, RET 541/3/5 and
REX 521.
Fig. 6.7.1.-1
SPA Communication Parameters
Locally, SPA-ZC 402 uses UTC (Coordinated Universal Time) time, which is
received from the SNTP time synchronization by default. This time format does not
use Daylight Saving Time. If you want that the IED and SPA communication uses
this time format, the IEC 61850 client has to be programmed to write the minute
offset of the UTC time to the LD0.LLN0. Daylight parameter at the defined date and
time depending on the location.

Downloading configuration and exporting CID file

After you have built the IEC 61850 data model and done the communication
addressing, you can download the configuration to SPA-ZC 402:
SPA-ZC 402
SPA-ZC 402
A040022
41