1MRS755380
4.11.
Fig. 4.11.-1 Downloading the device's configuration
SPA/ Ethernet Adapter
Installation and Commissioning Manual

Downloading configuration and exporting CID file

After you have built the IEC 61850 data model and done the SPA mapping, it is
possible to download the configuration to SPA-ZC 402. Select the IEC 61850
Device object and right-click to select the CID Export. You can also export the CID
file to your workstation's file system and use it in system level tools, for example to
configure your IEC 61850-8-1 client.
If you download configuration to SPA-ZC 402 the first time, change the IP address
from default address (192.0.2.10) to new IP address according to planned network
structure.
CET and SPA-ZC 402 have a checking mechanism to avoid IP addressing problems.
If you select another subnet against current IP address, CET cannot connect anymore
to SPA-ZC 402 after the configuration downloading. You have to change the used
IP address and workstation/laptop address to access the configuration again. If IP
address changes radically, CET asks if you are aware of it. If you accept the changed
subnet, SPA-ZC 402 resets used IP address and takes the new address in to use. If
you do not accept changes, SPA-ZC 402 uses the old IP address against the
configuration.
SPA-ZC 402
A040029
49