Quick start-up guide

Overview

This chapter presents the steps to take during the start-up of the
RETA-02 Ethernet Adapter module. For more detailed information,
see chapters
Network
elsewhere in this manual.
WARNING! Follow the safety instructions given in this manual and
the Hardware Manual of the drive.

Mechanical installation

• Insert the RETA-02 into its specified slot in the drive (SLOT2 for
ACS550, SLOT1 for ACS800).
• Fasten the two screws.

Electrical installation

• Connect the Ethernet network cable (RJ-45 connector) to the
RETA-02 module. Standard CAT 5 UTP or STP cables can be
used. Avoid parallel runs with power (e.g. motor) cables.

Drive configuration

• Power up the drive. In Modbus/TCP mode the "MODULE
STATUS" LED should be green. If the network cable is
connected to an active network, the green "LINK/ACTIVITY"
LED should also be lit or blinking. In PROFINET IO mode the
"MODULE STATUS" led should be blinking red because the
name of the device has not been assigned yet.
• The detailed procedure of activating the drive for
communication with the module is dependent on the drive type.
Normally, a parameter must be adjusted to activate the
Mechanical
configuration,
Master configuration
installation,
Electrical
installation,
and
Communication
Quick start-up guide
19