Goose; Configuring Horizontal Data - ABB SPA-ZC 400 Installation And Commissioning Manual

Table of Contents

Advertisement

SPA-ZC 400
6.11.
6.11.1.
52
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

GOOSE

GOOSE is used in substation automation for fast horizontal communication
between IEDs to send, for example, interlocking and blocking information.
According to the IEC 61850-8-1 standard, GOOSE consists of Ethernet
multicast messages. A message is an image of sent MMS dataset that is
defined in the CID configuration. The configuration is based on a standard
CID file created in CET for SPA-ZC 40x.
The GOOSE data is sent periodically in 802.1Q multicast frames over the
local network. When data changes, the GOOSE frame is sent several times in
a fast cycle to prevent data losses.
The GOOSE configuration can be used only for binary signals in
SPA-ZC 400 and REF 54_. Other IEDs are currently not supported.
Horizontal information is based on REF 54_ application and its COMM_IN/
COMM_OUT 31 and COMM_IN/COMM_OUT 32 bits. These in/out 32/32
bits of data can be configured in a REF 54_ application. The data is sent
between IED and SPA-ZC 400. Therefore it is possible to send and receive 32
single bits horizontal data.
In GOOSE sending data is based on dataset and GOOSE Control Block
(GoCB). Dataset defines what kind of data is sent in the GOOSE frame.
GoCB links the GOOSE Control Block structure and its information to data.
The GoCB attributes are:
Multicast address
*
A multicast address can be used by several devices or it can be IED-
specific.
802.1 tagging info: APPID, priority and VLAN
*
APPID is the GoCB-specific integer which identifies the sender GoCB
and its data. Priority and VLAN group can be used in a local network;
default values are available. VLAN group can be used to filter messages in
a subnet.
GoCB name
*
The GoCB name is the name of the structure seen from the IEC 61850/
MMS client.
GoID
*
GoID is a GOOSE control block specific string.
Dataset definition
*
ConfRev
*

Configuring horizontal data

Horizontal data is sent in a standard SCL file and its GoCB and dataset
configuration.
1MRS755347

Advertisement

Table of Contents
loading

Table of Contents