Features

SPA-ZC 400 has the following features:
IEC 61850 connectivity for REF 541/3/5 , REM 543/5 and RET 541/3/5
*
Easy-to-use configuration tool for the IEC 61850 data mapping
*
Simultaneous dual port communication (SPA-ZC400EMP and SPA-
*
ZC400EMG versions) for IEC 61850 and LON/SPA (excluding event
polling)
Support of communication over TCP/IP
*
All relay data can be routed through SPA-ZC 400. The process data (status,
measurements and commands) is routed through the IEC 61850 bus and the
rest of the available data can be routed through SPA over TCP/IP.
Only one SPA client can be configured to poll SPA events from
the device. By default SPA-ZC 400 is configured to poll SPA
events, then it is not allowed to poll SPA events from another
SPA client.
If the event polling is disabled, the timestamp accuracy depends
on the IED configuration and the SPA bus speed.