1MRS755347
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
When the IEC 61850 client has been notified of the incoming record, the
client should read the COMTRADE files from SPA-ZC 400 by using FTP or
IEC 61850 File Transfer connection. The client must remove the files after
successful reading to maintain free space for forthcoming records. The files
are named as follows:
File name
yymmddnn.cfg
yymmddnn.dat
yymmddnn.inf
The filename consists of the following parts:
Part
yy
mm
dd
nn
Example
Description
70010104.cfg
Configuration file
70010104.dat
Data file
70010104.inf
Information file
Format
Description
00 – 99
Record creation timestamp, year
01 – 12
Record creation timestamp, month
01 – 31
Record creation timestamp, date
00 - 99
Running serial number of the records of
the same day. The Configuration, Data
and Information files related to one
record have the same serial number.