ABB SPA-ZC 400 Installation And Commissioning Manual page 51

Table of Contents

Advertisement

1MRS755347
Fig. 6.10.-2
Report Control Block
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Buffered reporting needs mandatory Report Client definitions. Report Client
definitions link a certain RCB to a certain client. The client can import the
CID file to check what RCB instance it has to use. If Max property is defined
to 2, the configuration must have two clients with buffered reporting. In the
list first defined client uses the first RCB instance (rcb name ...01) and the
second RCB uses second instance (rcb name ...02 ). It is not mandatory to
define clients in unbuffered reporting, but it is recommended for clarity.
Client IED Name has to match with the client name in Substation
Configuration description Language (SCL).
Every modification in RCB increases the rcb Configuration Revision
property by one. Each revision generates the CID file and the IEC 61850
client can check between the received revision and file configuration revision.
SPA-ZC 400
A040134B
51