1MRS755347
6.4.3.
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
You can have a maximum of two Logical Device objects under
one Device Object (LD0 and one IED logical node).
When the actual IEC 61850 data model is created, the logical device name
has two parts:
Device Object name
*
Logical Device name
*
for example, REF543_F1LD0.

Importing IEC 61850 data object model of IED

1. Right-click to select a Logical Device object (for example, REF 541/3/5).
2. Import the project created with CAP 505, the Relay Product Engineering
Tools software.
The imported file, which is in the specified directory, is a compressed archive
file from CAP 505 Application Library with the file extension .AR.
Communication Engineering Tool (CET) for SPA-ZC 40x converts the
project files with the help of the Connectivity Packages to a IEC 61850 data
object model.
The Connectivity Package does not necessarily support all the functions of
IED. The functions, which are not mapped to the IEC 61850 structure, are
reported after import.
The tool imports default data sets and report control blocks (RCB) to logical
device LD0, see Fig. 6.4.3.-1. Data sets include a set of selected data
attributes from IED's IEC 61850 data model. These data sets are used in the
IEC 61850 event reporting model. If data attributes are selected to the data set
and the same data set is used in report control block (RCB), the data set
generates a spontaneous event which will be sent to the IEC 61850 client. If
the data set is not defined in the RCB, the IEC 61850 client reads the data
separately. You can modify data sets with Dataset Editor, see
Section 6.5. Using Dataset Editor.
After adding a new relay, give the IED with the unique name in
the network. Space is not allowed on the IED's name. Renaming
can be done in the Project Explorer dialog, see Fig. 6.4.3.-1.