Configuration connection method 1

To connect to SREA-01, use an Ethernet cable. Configure your PC to the same
subnet (e.g. IP address 10.200.1.2 and subnet mask 255.255.255.0, other settings
blank).
Use Internet Explorer or Mozilla Firefox and go to location http://10.200.1.1.

Configuration connection method 2

Install the ABB IP Configuration Tool from the attached CD. When you start the
program, it will search for connected SREA-01 modules. You can change the
network settings of the module by double clicking it.
Use Internet Explorer or Mozilla Firefox and go to location
http://<ip of the SREA-01 module>, e.g. http://10.200.1.1.
Note: Make sure that your web browser is not using a proxy server for local
connections.

Basic settings of the drive(s)

You should check the communication settings of the drive. Station id/number has
to be unique for each drive! The baud rate selection and parity have to be same on
all drives and SREA-01. You can use for example 9600 bit/s, no parity, 1 stop bit.
For settings and parameter groups, see the drive template guide.

Most important settings of SREA-01

You can change the Ethernet settings under Setup – Ethernet. The login password
can be changed under Setup – Users.
Select the correct drive connection settings under Setup – Modbus.
• Select Physical Interface. If you are using the supplied RJ45-ended cable,
select RS-232. If you are using the OPCA-02 cable, select RS-232 (D-sub). If you
are using RS-485, select RS-485.
• Usually most other settings are suitable by default. (RTU, 9600 bps, No parity, 1
Stop bit)
To search for connected drives, go to page Configuration – Devices and select
autodetect.