Installation and Commissioning Manual

Test and conditions

Table 8.2.-1
Environmental test and conditions
Recommended service temperature
range (continuous)
Transport and storage temperature
range
Dry heat test
Dry cold test
Damp heat test, cyclic
Table 8.2.-2
Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below.
1 MHz burst disturbance test, class III According to the IEC 60255-22-1
Common mode
*
Differential mode
*
Electrostatic discharge test, class III
For contact discharge
*
For air discharge
*
Radio frequency interference tests
Conducted, common mode
*
Radiated, amplitude-modulated
*
Radiated, pulse-modulated
*
Fast transient disturbance tests
All terminals
*
Surge immunity test
Power supply
*
Power frequency (50 Hz) magnetic
field IEC 61000-4-8
Electromagnetic emission tests
Conducted, RF-emission (Mains
*
terminal)
Radiated RF-emission
CE approval
SPA-ZC 400
-10...+55˚C
-40...+70˚C according to the IEC 60068-2-
48
According to the IEC 60068-2-2
According to the IEC IEC 60068-2-1
According to the IEC 60068-2-30
2.5 kV
1.0 kV
According to the IEC 61000-4-2 and
IEC 60255-22-2
6 kV
8 kV
According to the IEC 61000-4-6 and
IEC 60255-22-6 10 V (rms), f=150 kHz...80
MHz
According to the IEC 61000-4-3 and
IEC 60255-22-3 10 V/m (rms), f=80...1000
MHz
According to the ENV 50204 and IEC 60255-
22-3 10 V/m, f=900 MHz
According to the IEC 60255-22-4 and
IEC 61000-4-4
4 kV
According to the IEC 61000-4-5
4 kV, line-to-earth 2 kV, line-to-line
300 A/m continuous
According to the EN 55011
EN 55011, class A, IEC 60255-25
EN 55011, class A, IEC 60255-25
Complies with the EMC directive 89/336/
EEC and the LV directive 73/23/EEC