Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1. Right-click to select an IEC 61850 Device object (SPA-ZC 40x) and select
New > Communication > Logical Device. This generates the mandatory
logical device LD0, logical node LLN0 and its data structure for
SPA-ZC 400. Logical device LD0 describes SPA-ZC 400 and includes the
data objects for diagnostics and description. All data sets and report
control blocks (RCB) will be collected to LLN0.
2. Add a new Logical Device object (REF 541/3/5), see Fig. 6.4.2.-1. This is
possible only after you have installed Connectivity Packages to your
computer. The IED's data model behind SPA-ZC 400 is described in the
logical device LD1.
For more information about installing Connectivity Packages, refer to
Section 5.3. Installing Connectivity Packages.
Fig. 6.4.2.-1
Adding Logical Device objects
The logical device object is now shown as a sub-object to the IEC 61850
Device object, see Fig. 6.4.2.-2.
Fig. 6.4.2.-2
Logical node is shown as sub-object
You should have at least one Logical Device object as a child
object to each IEC 61850 Device Object.