54 Modbus/TCP – Start-up

Drive configuration

The information in this section applies to all drive types compatible
with the adapter module, unless otherwise stated.

Modbus/TCP connection configuration

After the adapter module has been mechanically and electrically
installed according to the instructions in chapters
installation
and
Electrical
for communication with the module.
The detailed procedure of activating the module for Modbus/TCP
communication with the drive depends on the drive type. Normally,
you must adjust a parameter to activate the communication. See
the drive-specific start-up sections starting on page 67.
Once communication between the drive and the adapter module is
established, several configuration parameters are copied to the
drive. These parameters are shown in the tables below and must
be checked first and adjusted where necessary. You can adjust the
parameters via a drive control panel, a PC tool or a web user
interface. For more information on the web user interface, see
Appendix C – FENA configuration web
Note:
Not all drives display descriptive names for the configuration
parameters.
The new parameter settings take effect only when you power
up the module the next time or when you activate the fieldbus
adapter refresh parameter.
installation, you must prepare the drive
pages.
Mechanical