Maintenance And Service; Led Indicators; Communication Settings - ABB SPA-ZC 400 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS755347
9.
9.1.
Table 9.1.-1

LED indicators

LED
Color
Power
Green
Link LAN
Green
RX
LAN
Green
TX
LAN
Green
DIAG
Green
Red
RX
Green
9.2.
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

Maintenance and service

If the SPA-ZC 400 module or a part of it is found to be faulty, the normal
service operation is to replace the entire module. For more details, refer to
Table 13.-1.
LED indicators
State
On
On
On
On
Off
On
Flashing
On
On
On
Flashing
Off
On
Off
Off
Flashing
On
Possible sequences are:
1 → 3 → 5
Normal situation
1 → 2
Missing boot image
1 → 3 → 4
Configuration file is missing
1 → 3 → 6
Configuration error
If configuration error is detected because of the mismatches in
downloaded the CID file, download a simpler configuration.
Check also the log file in SPA-ZC 400.

Communication settings

REF 541/3/5, REM 543/5 and RET 541/3/5 addresses or baud rates are not
properly defined if:
Diagnostic counter SPAReplyTimo increases constantly and
*
SPAReplyData remains 0 in the LDO.LLNO.ComDiag data object.
These diagnostic counters are readable from the IEC 61850 client.
Quality of the data is INVALID.
*
Sequence
Description
number
Power on
Indication for LAN link OK
Indication for incoming LAN traffic
Indication for outgoing LAN traffic
1
Bootloader booting
2
Bootloader, missing boot image
3
Starting
4
OK, missing configuration
5
OK, configuration in use
6
Configuration error
Indication for incoming LON traffic
(LON and SPA)
SPA-ZC 400
67

Advertisement

Table of Contents
loading

Table of Contents