SPA-ZC 400
50
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
Option Field
*
Defines what information is sent with report
By default SPA-ZC 400 adds buffer over-flow information, report
entryID, sequence number and allows segmentation. Other fields are
RCB configuration version, data reference in MMS address format, name
of the used data set and report sending time.
Max property
*
Defines how many clients are using this RCB, the number of needed RCB
instances. If you define two clients for buffered reporting, then Max has to
be 2. SPA-ZC 400 creates two instances of RCB name, for example,
rcbStatNrml01 and rcbStatNrml02. For unbuffered reporting, Max has to
be same as the number of defined clients or higher. This is defined in the
IEC 61850 standard.
Trigger Options
*
Data Change, Data Update and Quality Change triggers are used by
default (changes in value and quality generates information reports).
Period trigger is not used by default.
1MRS755347