FBIP-21 configuration parameters – group A
(group 1)
Group A (group 1) corresponds to parameter group 51 in ACH580
drive.
No.
Name/Value
01
FBA type
0 = None
47808 =
BACnet
02
Reserved
03
Commrate
0 = Auto
1 = 100 Mbps
FD
2 = 100 Mbps
HD
3 = 10 Mbps FD 10 Mbps, full duplex
4 = 10 Mbps HD 10 Mbps, half duplex
04
IP configuration
0 = Static IP
1 = Dyn IP
DHCP
Description
Shows the fieldbus adapter type as
detected by the drive. You cannot
adjust this value.
This parameter is read-only.
Communication between the drive and
the module is not established.
BACnet
This parameter is not used by the
adapter module.
Sets the bit rate of the communication
and determines if the communication
can be simultaneously two-way (full
duplex) or only one way (half duplex).
Auto-negotiate
100 Mbps, full duplex
100 Mbps, half duplex
Sets the method for configuring the IP
address, subnet mask and gateway
address for the Ethernet interface.
Configuration will be obtained from
parameters 05...13.
Configuration is obtained via DHCP.
Start-up 29
Default
47808 =
BACnet
-
0 = Auto
1 = Dyn
IP
DHCP