SPA-ZC 400
16
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
5. Install a new IED by right-clicking the IEC 61850 device and selecting
New > Communication. Select the appropriate IED type and rename the
IED with the unique name.
Each IEC 61850 name has to be unique in each level (IED, LD,
LN, DO).
6. Import the IED application to logical device LD1 by right-clicking LD1
and selecting the AR file, which contains the IED application.
7. Set the IP address to SPA-ZC 40x in Object Properties pane.
Default Gateway
*
IP Address
*
SNTP Server 1 and 2
*
Subnet mask
*
Refer to Section 5.4.1. Changing computer's IP address.
8. Set Time Zone Correction.
9. Rename the IED, for example REF545_F1.
10.Adjust IED SPA Communication parameters in the Object Properties
pane.
11.Adjust network adapter's IP address to same subnet as SPA-ZC 400. To
perform the operation, open Windows XP Network Connections in
Control Panel.
If CID file exists, the IP address is read from the file. Otherwise, the
default IP address of SPA-ZC 400 is 192.168.2.10.
Use IP Query Tool to find out an unknown IP address.
12.Use CID Export tool to transfer the configuration file to SPA-ZC 40x.
13.Export CID or ICD file for the IEC 61850 client.
1MRS755347