Installation; Mechanical Installation; Communication Engineering Tool For Spa-Zc 40X; System Requirements - ABB SPA-ZC 400 Installation And Commissioning Manual

Table of Contents

Advertisement

1MRS755347
5.
5.1.
5.2.
5.2.1.
5.2.2.
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

Installation

This chapter describes the installation of the SPA-ZC 400 module and the
Communication Engineering Tool (CET) for SPA-ZC 40x. For additional
information, such as technical data, maintenance and service, refer to
Section 8. Technical data and Section 9. Maintenance and service.

Mechanical installation

Connect the SPA-ZC 400 module to REF 541/3/5, REM 543/5 or
RET 541/3/5 and screw SPA-ZC 400 to the 9-pin type D-connectors. Connect
the LAN cable to the LAN connector of SPA-ZC 400. The other end of the
cable is connected to the IEC 61850 Station bus through the Ethernet switch.

Communication Engineering Tool for SPA-ZC 40x

System requirements

Communication Engineering Tool (CET) for SPA-ZC 40x runs on Windows
2000, Windows XP and Windows Server 2003 operating systems. A PC
capable of running one of these operating systems is sufficient also for CET
for SPA-ZC 40x. For more information, refer to
Section 1.4. Product documentation. The detailed system requirements can be
seen below.
20 MB free hard disk space if Microsoft .NET Framework 1.1, which is
*
required for running CET for SPA-ZC 40x, has already been installed.
100 MB free hard disk space, if the Microsoft .NET Framework 1.1 is not
*
installed. It is installed automatically if it is not found.

Installing Communication Engineering Tool for SPA-ZC 40x

1. Uninstall the previous version.
2. Close all the open programs and insert the Communication Engineering
Tool (CET) for SPA-ZC 40x installation CD to the CD-ROM drive of your
PC.
3. The Installation program starts automatically. If this is not the case, open
the program by starting setup.exe on the CD drive.
4. The installation wizard extracts the installation files to your local
computer.
SPA-ZC 400