ABB SPA-ZC 400 Installation And Commissioning Manual page 97

Table of Contents

Advertisement

1MRS755347
Table 11.2.2.18.-1 Controllable integer status (INC)
INC class
Attribute
Attribute Type
Name
DataName
Inherited from Data Class (refer to IEC 61850-7-2)
DataAttribute
ctlVal
CtxInt
operTm
TimeStamp
origin
Originator
ctlNum
INT8U
stVal
INT32
q
Quality
t
TimeStamp
stSeld
BOOLEAN
subEna
BOOLEAN
subVal
ValWithTrans
subQ
Quality
subID
VISIBLE
STRING64
persistent
BOOLEAN
ctlModel
ENUMERATED
sboTimeout
INT32U
sboClass
ENUMERATED
minVal
INT8
maxVal
INT8
stepSize
INT8U
d
VISIBLE
STRING255
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
FC
Control and Status
CO
CO
ST
ST
ST
ST
ST
ST
Substitution
SV
SV
SV
SV
Configuration, Description and Extension
CF
CF
CF
CF
CF
CF
CF
DC
Value/ Value
TrgOp
range
0..255
dchg
qchg
dchg
Status-only |
direct-with-
normal-security
| sbo-with-
normal-security
| direct-with-
enhanced-
security | sbo-
with-enhanced-
security
operate-once |
operate-many
1 ... (maxVal -
minVal)
Text
SPA-ZC 400
SPA-ZC 400/
M/O/C
Comments
Supported
AC_CO_M
Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
M
Supported
M
Supported
M
Supported
AC_CO_O
Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
PICS_SUBST Not Supported
M
Not Supported
M
Supported
AC_CO_O
Not Supported
AC_CO_O
Not Supported
O
Not Supported
O
Not Supported
O
Not Supported
O
Supported