1MRS755347
6.11.1.1.
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1. Create a GOOSE Control Block (GoCB) under LD0.LLN0.
The names of the GoCB and the dataset should be unique within
the IED. Maximum length should be 10 characters.
2. Right-click LLN0 and select New > GOOSE > GoCB to link an existing
dataset to it from Object properties. Both GOOSE Control Block and
dataset should be located under LLN0. After creating a GOOSE Control
Block, CET for SPA-ZC 40_ creates automatically the following logical
nodes:
CIGGIO31/32
*
COGGIO31/32
*
The logical nodes can be accessed through the REF 54_ application.
COMM_IN31, COMM_IN32, COMM_OUT31 and COMM_OUT32 are
used for single binary information, and therefore bits can be accessed through
the SPS object. For example LD0.LNN0.COGGIO32.Ind13 refers to
COMM_OUT32 bit 13 of the 16 possible.

GOOSE TX dataset

To send the GOOSE configuration, you must the sending dataset. To build a
dataset:
1. Create and rename it (refer to Section 6.5. Using Dataset Editor).
2. Drag and drop the data objects in Dataset Editor.
The data attributes that are not needed must be deleted in this phase, for
example the t attribute which is normally not needed in horizontal
communication.
The GOOSE dataset is exported from the attribute level, and therefore the
Data Object structures are not sent. When sending COGGIO.Ind single point
binaries, only the stVal status attribute is sent, because the quality or time
information is not accessible from RE_54_ COMM_OUT. The quality
information is linked to the internal IED communication link status which can
be forwarded.
In DPC Data Objects, for example in CSWI, the boolean stSeld Data
Attribute is generated inside the SPA-ZC 40_IEC 61850 command handler
and it is a faster way to send blocking data.
It is not recommended to build horizontal data from normal
event-based polled data because it is slow in load situations.
SPA-ZC 400
53