ABB SPA-ZC 400 Installation And Commissioning Manual

ABB SPA-ZC 400 Installation And Commissioning Manual

Table of Contents

Advertisement

Quick Links

Ethernet Adapter
SPA-ZC 400
SPA to IEC 61850 Gateway
Installation and Commissioning Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB SPA-ZC 400

  • Page 1 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual...
  • Page 3: Table Of Contents

    5.3. Installing Connectivity Packages........25 5.3.1. Enabling Connectivity Packages......26 5.3.2. Uninstalling Connectivity Packages....27 5.4. Connecting to SPA-ZC 400..........27 5.4.1. Changing computer's IP address....... 27 5.4.2. Checking connection to SPA-ZC 400....28 6.
  • Page 4 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 6.6. Configuring by using imported CID file......40 6.7. Configuring communication parameters......40 6.7.1. SPA Communication parameters......41 6.8. Downloading configuration and exporting CID file.... 43 6.8.1.
  • Page 5 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.8. Vector definition........79 11.2.1.9. CTxInt..........79 11.2.2. Common data classes........79 11.2.2.1. Single point status (SPS)....79 11.2.2.2. Double point status (DPS)....80 11.2.2.3.
  • Page 6 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 13. Ordering information............115 14. Terminology..............117 15. Abbreviations..............119...
  • Page 7: Copyrights

    Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. In no event shall ABB Oy be liable for direct, indirect, special, incidental or...
  • Page 9: Introduction

    This manual This manual provides thorough information on the SPA-ZC 400 Ethernet Adapter and the central concepts related to it. SPA-ZC 400 Ethernet Adapter is used for connecting REF 541/3/5, REM 543/5 and RET 541/3/5 Intelligent Electronic Devices (IED) to the IEC 61850 Station bus. In the manual you find information on SPA-ZC 400 and its components, an introduction to engineering tasks and a description of the basic operations.
  • Page 10: Intended Audience

    This manual is intended for installation personnel, administrators and skilled operators to support installation of the software. 1.4. Product documentation Name of the manual Document ID SPA-ZC 400 configuration CD 1MRS151048 CAP 505 User's Guide 1MRS752292-MUM SPA-ZF Optical glass fibres, multimode 1MRS755371...
  • Page 11: Revision History

    You may be told to enter the string MIF349 in a field. The string is shown as follows in the procedure: Example: MIF349 Variables are shown using lowercase letters: sequence name 1.6. Revision history Version Date History 06.10.2004 Document created 11.10.2004 Document updated 30.12.2004 Ordering information changed 30.06.2006 SPA-ZC 400 2.0 additions...
  • Page 13: Safety Information

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Safety information Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed.
  • Page 15: Quick Start

    Installation and Commissioning Manual Quick start 1. Install Communication Engineering Tool (CET) for SPA-ZC 40x and Connectivity Packages. Download the latest Connectivity Packages on the ABB web site (http://www.abb.com/substationautomation). 2. Activate the appropriate Connectivity Package by using Connectivity Package Manager, see Fig. 3.-1.
  • Page 16 9. Rename the IED, for example REF545_F1. 10.Adjust IED SPA Communication parameters in the Object Properties pane. 11.Adjust network adapter's IP address to same subnet as SPA-ZC 400. To perform the operation, open Windows XP Network Connections in Control Panel.
  • Page 17: Product Overview

    Installation and Commissioning Manual Product overview SPA-ZC 400 is used to connect one REF 541/3/5, REM 543/5 or RET 541/3/5 device to the IEC 61850 Station bus. The IEC 61850 standard defines the IEC 61850 communication and engineering specifications. In...
  • Page 18: Spa-Zc400Emp And Spa-Zc400Emg

    Installation and Commissioning Manual Media converters: RuggedCom RMC-100-MM IMC McBasic MM1300 Allied Telesyn AT-MC302-20 More tested devices can be found on the ABB web site (http://www.abb.com/substationautomation). 4.1. SPA-ZC400EMP and SPA-ZC400EMG SPA-ZC400EMP and SPA-ZC400EMG versions have the same IEC 61850 functionality as described in Section 4. Product overview. In addition, these versions include an optional fibre-optic interface.
  • Page 19: Features

    Support of communication over TCP/IP All relay data can be routed through SPA-ZC 400. The process data (status, measurements and commands) is routed through the IEC 61850 bus and the rest of the available data can be routed through SPA over TCP/IP.
  • Page 20: Iec 61850 Standard

    1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040138B Fig. 4.2.-1 Parts of SPA-ZC 400 1 Ethernet connector 2 LON/ SPA bus connector (optional) 3 LON/ SPA Rx LED 4 LON service pin 5 LAN and diagnostics LEDs 4.3.
  • Page 21 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Asset management Condition monitoring and diagnostics The IEC 61850 standard provides: Standardized information models for all kinds of protection relays, controllers, circuit-breakers, transformers, and so on.
  • Page 23: Installation

    RET 541/3/5 and screw SPA-ZC 400 to the 9-pin type D-connectors. Connect the LAN cable to the LAN connector of SPA-ZC 400. The other end of the cable is connected to the IEC 61850 Station bus through the Ethernet switch.
  • Page 24 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 5. The CET for SPA-ZC 40x Installation program starts. In this dialog, click Next. With the Back button you can return to the previous dialog, and with the Cancel button, exit the installation wizard.
  • Page 25: Uninstalling Communication Engineering Tool For Spa-Zc 40X

    5.3. Installing Connectivity Packages 1. Close all the open programs and insert the SPA-ZC 400 configuration CD to the CD-ROM drive of your PC. The Connectivity Packages can be downloaded on the ABB web site (http://www.abb.com/substationautomation).
  • Page 26: Enabling Connectivity Packages

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 4. The Connectivity Package Installation program starts. In this dialog, click Next. With the Back button return to the previous dialog, and with the Cancel button, exit the installation wizard. This applies to all the dialogs in the installation wizard.
  • Page 27: Uninstalling Connectivity Packages

    The Sections 5.4.1. and 5.4.2. Checking connection to SPA-ZC 400 describe how to connect to SPA-ZC 400 from the Communication Engineering Tool (CET) for SPA-ZC 40x. 5.4.1. Changing computer's IP address To connect SPA-ZC 400, the used computer and SPA-ZC 400 must use the same address space.
  • Page 28: Checking Connection To Spa-Zc 400

    SPA to IEC 61850 Gateway Installation and Commissioning Manual To change the computer's IP address space to be the same as in SPA-ZC 400: 1. Open the Network Connections in Control Panel. 2. Type, for example, the following IP address to the IP address box: 192.168.2.1.
  • Page 29 Pinging SPA-ZC 400 SPA-ZC 400 responds to the ping command if the computer and SPA-ZC 400 are on the same network. 5. If SPA-ZC 400 responds with the IP address, the connection is established between the computer and SPA-ZC 400.
  • Page 31: Engineering

    6.1. Overview of engineering The engineering and maintenance of SPA-ZC 400 is done by using CET for SPA-ZC 40x functions or by importing the existing SPA-ZC 40x CID file. The device's communication structure is described in the Project Explorer dialog.
  • Page 32: Creating Project

    Creating a new project 6.3. Restarting Use this function to restart the SPA-ZC 400 at runtime. 1. Select IED and Tools > Reset Tool to open the restart pane, see Fig. 6.3.-1 2. Click Reset. The results are reported to the UI text box.
  • Page 33: Building Object Tree

    Fig. 6.4.-1 shows an example of the object tree when it has been built. In the example tree you can see the SPA-ZC 400 object and its child objects as devices and data objects. Indentation is used to indicate the parent-child...
  • Page 34 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040137B Fig. 6.4.-1 Example view of the SPA-ZC 40x Communication Engineering Tool You have several possible ways to add objects to the object tree in the...
  • Page 35: Adding Device Object

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual 7. GOOSE control blocks 8. GOOSE inputs 6.4.1. Adding Device object To build the object tree: 1. Add an IEC 61850 Device object in the communication structure by selecting the project name.
  • Page 36 2. Add a new Logical Device object (REF 541/3/5), see Fig. 6.4.2.-1. This is possible only after you have installed Connectivity Packages to your computer. The IED's data model behind SPA-ZC 400 is described in the logical device LD1. For more information about installing Connectivity Packages, refer to Section 5.3.
  • Page 37: Importing Iec 61850 Data Object Model Of Ied

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual You can have a maximum of two Logical Device objects under one Device Object (LD0 and one IED logical node). When the actual IEC 61850 data model is created, the logical device name...
  • Page 38: Using Dataset Editor

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040026B Fig. 6.4.3.-1 Project Explorer dialog in the Communication Engineering Tool window 6.5. Using Dataset Editor The dataset groups selected data so that a client can access it easily with a single read operation.
  • Page 39 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual to the dataset. Data attributes are collected to the dataset in groups, and functional constraint defines the data attributes. This is MMS protocol's naming feature, which is the basic part of naming and protocol definition in the IEC 61850 standard.
  • Page 40: Configuring By Using Imported Cid File

    6.6. Configuring by using imported CID file If you have to configure several SPA-ZC 400 with the similar IEC 61850 data object model, it is possible to import a previously generated CID file and change the communication addresses, typically by changing the IP address.
  • Page 41: Spa Communication Parameters

    SPA Password is used for commands and it has to be the same as the defined password in the IED. SPA-ZC 400 has to know the SPA Password to write the data to IED. Password (SPA parameter 0V160) is needed only for controllable integer status (INC).
  • Page 42 In this mode, you can only synchronize SPA-ZC 400 with SNTP and IED has a different source of time synchronization. Read from device if supported When this operation mode is selected, the time for SPA-ZC 400 is read from IED over SPA. SNTP is not in use. SPA time synchronization parameter The parameter describes the SPA parameter which SPA-ZC 400 uses when reading the time from the IED.
  • Page 43: Downloading Configuration And Exporting Cid File

    1. Select the IEC 61850 Device object and right-click to select the CID Export. 2. If you download configuration to SPA-ZC 400 the first time, change the IP address from default address (192.168.2.10) to new IP address according to the planned network structure.
  • Page 44 Fig. 6.8.-1 Downloading the device's configuration If SPA-ZC 400 is connected to a system where the connection to it can be obtained, the Export function tries to determine the SPA-ZC 400 version and exports the export file accordingly. If the connection is disabled, prompt the correct version to be exported, see Fig.
  • Page 45: Ied Application Changes

    If a new functionality is added to the IED application, the new IED application (AR file) import is needed. In this case, there are two options: Communication Engineering Tool (CET) for SPA-ZC 400 asks either the old SPA-ZC 400 application is overwritten or only the new functionality is added.
  • Page 46 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040131B Fig. 6.9.-1 LN wizard 5. Select the new logical node in the project tree. 6. Right-click the logical node and select DO Wizard to start the DO Wizard, see Fig.
  • Page 47 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040132B Fig. 6.9.-2 DO Wizard 10.Start with the mandatory data objects and then add the process data. Mandatory data objects are Mod, Beh, Health and NamPlt.
  • Page 48 LN object. A040133B Fig. 6.9.-3 Data Object Instance Editor The SPA point data is written to the sAddr in the CID file for the selected data object. SPA-ZC 400 uses this field to poll data and events from the IED.
  • Page 49: Configuring Report Control Blocks

    Default value for Integrity Period is 0 ms. If this attribute has value > 0 ms, SPA-ZC 400 sends a report with all data listed in linked data set with this period. By default this feature is not enabled because it generates unnecessary load to server and network.
  • Page 50 Defines how many clients are using this RCB, the number of needed RCB instances. If you define two clients for buffered reporting, then Max has to be 2. SPA-ZC 400 creates two instances of RCB name, for example, rcbStatNrml01 and rcbStatNrml02. For unbuffered reporting, Max has to be same as the number of defined clients or higher.
  • Page 51 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040134B Fig. 6.10.-2 Report Control Block Buffered reporting needs mandatory Report Client definitions. Report Client definitions link a certain RCB to a certain client. The client can import the CID file to check what RCB instance it has to use.
  • Page 52: Goose

    COMM_OUT 31 and COMM_IN/COMM_OUT 32 bits. These in/out 32/32 bits of data can be configured in a REF 54_ application. The data is sent between IED and SPA-ZC 400. Therefore it is possible to send and receive 32 single bits horizontal data.
  • Page 53: Goose Tx Dataset

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual 1. Create a GOOSE Control Block (GoCB) under LD0.LLN0. The names of the GoCB and the dataset should be unique within the IED. Maximum length should be 10 characters.
  • Page 54: Defining Goose Control Block Properties

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 6.11.1.2. Defining GOOSE Control Block properties After creating sending dataset, start to configure GOOSE Control Block (GoCB): 1. Add the dataset to be sent in GOOSE.
  • Page 55: Configuring Goose Inputs

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Data-related multicast address. Received multicast addresses are stored to check the GOOSE message and they can be used as a hardware-specific Ethernet message filter. Multicast address is used as an IED-specific unique identifier.
  • Page 56: Goose Rx-Specific Features

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 6.11.2.2. GOOSE RX-specific features Only CIGGIO31 or CIGGIO32 logical nodes Ind data objects can receive single point status data (SPS). Every input can have its own target data attribute, for example, LD0.LNN0.CIGGIO31.Ind1.stVal or many inputs can...
  • Page 57 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual A060132 Fig. 6.12.-2 Configuring properties 5. Create reference to scale at DO level in object tree, see Fig. 6.12.-3...
  • Page 58: Using Disturbance Recorder Files

    IEC 61850 client after new files are ready to be read. A relay with compatible MEDREC16 function block notifies SPA-ZC 400 when it has new recordings ready. SPA-ZC 400 reads the actual data from the relay as a background process and stores the data as COMTRADE files in its...
  • Page 59 Installation and Commissioning Manual When the IEC 61850 client has been notified of the incoming record, the client should read the COMTRADE files from SPA-ZC 400 by using FTP or IEC 61850 File Transfer connection. The client must remove the files after successful reading to maintain free space for forthcoming records.
  • Page 61: Commissioning

    You can see how the configuration process is progressing from the diagnostic LEDs. When the SPA-ZC 400 configuration is completed, the green LED is If SPA-ZC 400 is online with the IEC 61850 client, you can check the general configuration status of SPA-ZC 400 from the data model LD0.LLN0.Health.
  • Page 62 The q attribute quality bits of the properly updated data objects indicate GOOD or DEFAULTED. If this is not the case, configurations between SPA-ZC 400 and REF 541/3/5, REM 543/5 or RET 541/3/5 are not identical. If all the data objects have INVALID quality, the SPA communication is not running.
  • Page 63: Technical Data

    Installation and Commissioning Manual Technical data 8.1. Interfaces SPA-ZC 400 - IED interfaces Fixed mechanics and fixed connectors for REF 541/3/5, REM 543/5 and RET 541/3/5 protection relays D-type subminiature connector for IEC 61850 traffic D-type subminiature connector for simultaneous dual port communication (optional, see Table 4.1.-1).
  • Page 64 IEC 61850 MODBUS / TCP SPA / TCP 00-0C-02-B0-CC-00 POWER LINK DIAG SERVICE ETHERNET A040130B Fig. 8.1.-1 Dimensions of the SPA-ZC 400 module Table 8.1.-1 Dimensions and weight Type Dimensions [mm] Weight [g] SPA-ZC 400 195 x 50 x 26...
  • Page 65: Test And Conditions

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual 8.2. Test and conditions Table 8.2.-1 Environmental test and conditions Recommended service temperature -10...+55˚C range (continuous) Transport and storage temperature -40...+70˚C according to the IEC 60068-2-...
  • Page 66 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 8.2.-3 Standard tests Mechanical tests Vibration tests (sinusoidal) According to the IEC 60255-21-1, class I Shock and bump test According to the IEC 60255-21-2, class I Table 8.2.-4...
  • Page 67: Maintenance And Service

    SPA to IEC 61850 Gateway Installation and Commissioning Manual Maintenance and service If the SPA-ZC 400 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to Table 13.-1.
  • Page 68 Installation and Commissioning Manual The following IED-specific settings have to be checked when setting up REF 541/3/5, REM 543/5 or RET 541/3/5: Protocol selection for SPA-ZC 400 Table 9.2.-1 explains the possible port configurations of REF 541/3/5, REM 543/5 or RET 541/3/5.
  • Page 69: Ip Query

    SPA command timeout should be < 1 second when LON interlocking is not in use. SPA baud rate and SPA slave number in IED Baud rate and slave number have to be according to the SPA-ZC 400 configuration in X3.2/Communication 2. 9.3.
  • Page 70: Identification

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual A060128 Fig. 9.3.-2 Selecting Network adapter 3. Click Start to start the query. 4. Click Stop to stop the query. Connected devices are displayed in the Output pane, Fig. 9.3.-2.
  • Page 71: Obtaining Error Logs

    Installation and Commissioning Manual Select Help > About to view the version information. SPA-ZC 400 version information The version information can be read from the device's label. If the device is updated afterwards, use CET's IP query to get the correct version information from the device memory.
  • Page 73: Troubleshooting

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Troubleshooting Communication to SPA-ZC 40x is not working If communication problems occur, check the firewall configurations. Table 10.-1 shows the ports that have to be open in firewall.
  • Page 75: Technical Reference

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Technical reference This chapter defines the compliance to IEC 61850 in terms of service, modeling, engineering interfaces and also exceptions and local adaptations. The information gives you a detailed explanation of the IEC 61850 capabilities of a product.
  • Page 76: Model Conformance Statement

    In this chapter the Model Implementation Conformance Statement (MICS) is defined detailing the standard data object model elements supported by SPA-ZC 400. It is also possible to export the information in MICS to a CID file. The CID file can be used in the system tool, see Safety information.
  • Page 77: Analogue Value

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.1.1.-1 Quality (Continued) Quality Type Definition Value/ Value SPA-ZC 400/ Attribute Name AttributeType M/O/C Range Comments badReferer- BOOLEAN Defaulted ence oscillatory BOOLEAN Defaulted failure BOOLEAN...
  • Page 78: Range Configuration

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.4. Range configuration Table 11.2.1.4.-1 Range configuration RangeConfig Type Definition SPA-ZC 400/ Attribute Name AttributeType Value/ Value Range M/O/C Comments hhLim AnalogueValue Supported hLim AnalogueValue Supported...
  • Page 79: Unit Definition

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.1.6.-2 Values for orCat (Continued) Value Explanation automatic-station Control operation issued from an automatic function at station level automatic-remote Control operation issued from an automatic function...
  • Page 80: Double Point Status (Dps)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.1.-1 Single point status (SPS) SPS class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 81: Integer Status (Ins)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.2.-1 Double point status (DPS) (Continued) DBS class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments subVal INT32 PICS_SUBST Not Supported...
  • Page 82: Protection Activation Information (Act)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.3.-1 Integer status (INS) (Continued) INS class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255...
  • Page 83: Directional Protection Activation Information (Acd)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Different variants of the type exist based on the connectivity package short address information (sAddr). Underlined information indicates the basic type. 11.2.2.5. Directional protection activation information (ACD) Table 11.2.2.5.-1 defines the common data class of directional protection...
  • Page 84: Security Violation Counting (Sec)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.5.-1 Directional protection activation information (ACD) (Continued) ACD class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported...
  • Page 85: Measured Value (Mv)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.7.-1 Binary counter reading (BCR) BCR class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 86: Complex Measured Value (Cmv)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.8.-1 Measured value (MV) (Continued) MV class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments Quality qchg Supported TimeStamp Supported Substitution...
  • Page 87 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.9.-1 Complex measured value (CMV) CMV class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 88: Wye

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Different variants of the type exist based on the connectivity package short address information (sAddr). Underlined information indicates the basic type. 11.2.2.10. Table 11.2.2.10.-1 defines the common data class of WYE.
  • Page 89: Sequence (Seq)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.11.-1 Delta (DEL) SAV class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 90: Harmonic Value (Hmv)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.12.-1 Sequence (SEQ) (Continued) SAV class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments seqT ENUMERATED pos-neg-zero | Supported dir-quad-zero M Configuration, Description and Extension A | B | C | …...
  • Page 91: Harmonic Value For Wye (Hwye)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.13.-1 Harmonic Value (HMV) (Continued) HMV class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments VISIBLE Text Not Supported STRING255 cdcNs...
  • Page 92: Harmonic Value For Del (Hdel)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.14.-1 Harmonic value for WYE (HWYE) (Continued) HWYE class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments neutHar ARRAY[0.. dchg, dupd...
  • Page 93 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.15.-1 Harmonic value for DEL (HDEL) HDEL class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 94: Controllable Single Point (Spc)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.16. Controllable single point (SPC) Table 11.2.2.16.-1 defines the common data class of controllable single point. Table 11.2.2.16.-1 Controllable single point (SPC) SPC class Attribute Value/ Value...
  • Page 95: Controllable Double Point (Dpc)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.16.-1 Controllable single point (SPC) (Continued) SPC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported...
  • Page 96: Controllable Integer Status (Inc)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.17.-1 Controllable double point (DPC) (Continued) SPC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments subQ Quality PICS_SUBST Not Supported...
  • Page 97 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.18.-1 Controllable integer status (INC) INC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 98: Binary Controlled Step Position Information (Bsc)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.18.-1 Controllable integer status (INC) (Continued) INC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments cdcNs VISIBLE AC_DLNDA_M Supported STRING255...
  • Page 99: Integer Controlled Step Position Information (Isc)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.19.-1 Binary controlled step position information (BSC) (Continued) BSC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments Configuration, Description and Extension...
  • Page 100 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.20.-1 Integer controlled step position information (ISC) ISC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (see IEC 61850-7-2)
  • Page 101: Controllable Analogue Set Point Information (Apc)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Status-only is supported for the ctlModel. 11.2.2.21. Controllable analogue set point information (APC) Table 11.2.2.21.-1 defines the common data class of controllable analogue set point information.
  • Page 102: Integer Status Setting (Ing)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.22.-1 Single point setting (SPG) APC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 103: Analogue Setting (Asg)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.23.-1 Integer status setting (ING) (Continued) APC class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments CdcNs VISIBLE AC_DLNDA_M Not Supported...
  • Page 104: Device Name Plate (Dpl)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.25.-1 Setting curve (CURVE) ASG class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
  • Page 105: Logical Node Name Plate (Lpl)

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.26.-1 Device name plate (DPL) (Continued) ASG class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments hwRev VISIBLE Supported STRING255 swRev...
  • Page 106: Curve Shape Description (Csd)

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.3.-1 Logical node name plate (LPL) (Continued) ASG class Attribute Value/ Value SPA-ZC 400/ Attribute Type TrgOp M/O/C Name range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported...
  • Page 107: Scl Conformance Statement

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.3.1.-1 Curve shape description (CSD) (Continued) CSD class SPA- Value/ Attribute ZC 400/ Attribute Name TrgOp Value M/O/C Type Com- range ments crvPts ARRAY [1..
  • Page 108 SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table footnotes from previous page The CID file is used to configure the device. Notice that you have to preserve the SPA-ZC 40x Communication Engineering Tool's (CET) private sections to configure a device again.
  • Page 109: Scl Control Block

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.3.-3 Additional MMS services for SCL.2 and SCL.3 (Continued) SCL conformance Client-CR Server-CR Value/ SPA-ZC 400/ Base Base Range Comments GetDomai- nAttributes Supported LoadDomain Supported...
  • Page 110: Mms Conformance

    SPA-ZC 400 Ethernet Adapter 1MRS755347 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.5.1.-1 A-profile support SPA-ZC 400/ Client Server Comments Client/Server Supported A-Profile GOOSE/GSE Not Supported Management A-Profile GSSE A-Profile Not Supported TimeSync A- Not Supported Profile Must be m if support for any service specified for Client/S are declared within the ACSI basic conformance.
  • Page 111 1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.5.1.2.-1 GOOSE conformance (Continued) Subscriber Publisher SPA-ZC 400/Comments GetGOOSEElementNumber Not Supported GetGoCBValues Not Supported SetGoCBValues Not Supported GSENotSupported Not Supported GOOSE Control Block Not Supported (GoCB) Must be m if support is declared within ACSI basic conformance.
  • Page 113: Kema Certificate

    1MRS755347 Ethernet Adapter SPA-ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual KEMA certificate A060010...
  • Page 115 OK. Then select Download tab and from the Document kind drop-down list, select Software. Finally, click the Connectivity Package link to download it. Table 13.-1 Compatibility between IEC 61850 SPA-ZC 400, CET, Connectivity Packages and IEDs SPA-ZC 40x CET version...
  • Page 117 Furthermore, they can be used as IED internal identification for the attribute. Data communication protocol developed by ABB Connector type for glass fibre cable...
  • Page 119 Local Operating Network Manufacturing Message Specification Report Control Block SCADA Supervision, Control and Data Acquisition Substation Configuration Language (defined by IEC 61850) SNTP Simple Network Time Protocol Data communication protocol developed by ABB</ para> Structured Query Language Extended Markup Language...
  • Page 122 ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND +358 10 2211 +358 10 224 1080 www.abb.com/substationautomation...

Table of Contents