SPA-ZC 402 Ethernet is used for connecting any Intelligent Electronic Devices (IED), which provides fibre-optic SPA bus, to the IEC 61850 Station bus. In the manual you find information on SPA-ZC 402 and its components, an introduction to engineering tasks and a description of the basic operations.
Plastic-core fibre-optic cables, Features and 1MRS752089 instructions for mounting Connectivity Packages, User's Guide 1MRS755312 The Connectivity Packages can be downloaded on the ABB web site http://www.abb.com/ substationautomation. Related IEC 61850 standards: IEC 61850-6: Configuration description language for communication in electrical substations related to IEDs...
Variables are shown using lowercase letters: sequence name 1.6. Revision history Version Date History 23.11.2004 Document created 30.12.2004 Ordering information updated 31.01.2005 Table 8.2.-2 Surge immunity updated 30.06.2006 SPA-ZC 402 2.0 additions 16.2.2007 SPA-ZC 402 2.1 additions 20.05.2009 SPA-ZC 402 2.1.2 additions...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Safety information Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation.
Installation and Commissioning Manual Quick start 1. Install Communication Engineering Tool (CET) for SPA-ZC 40x and Connectivity Packages. Download the latest Connectivity Packages on the ABB web site http://www.abb.com/substationautomation. 2. Activate the appropriate Connectivity Package by using Connectivity Package Manager, see Fig. 3.-1.
Page 16
9. Rename the IED, for example REF545_F1. 10.Adjust IED SPA Communication parameters in the Object Properties panel. 11.Adjust network adapter's IP address to same subnet as SPA-ZC 402. To perform the operation, open Windows XP Network Connections in Control Panel.
Installation and Commissioning Manual Product overview SPA-ZC 402 is used to connect one IED with the fibre-optic SPA bus to the IEC 61850 Station bus. The IEC 61850 standard defines the IEC 61850 communication and engineering specifications. SPA-ZC 402 offers also the possibility to access the device with the SPA protocol over the TCP/IP network using the same Ethernet link.
Easy-to-use configuration tool for the IEC 61850 data mapping Support of communication over TCP/IP All relay data can be routed through SPA-ZC 402. The process data (status, measurements and commands) is routed through the IEC 61850 bus and the rest of the available data can be routed through SPA over TCP/IP.
SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040157B Fig. 4.1.-1 Parts of SPA-ZC 402 1 Ethernet connector 2 Fibre-optic SPA bus connectors 3 Auxiliary power supply connector 4 SPA TX and RX LEDs 5 LAN and diagnostics LEDs 4.2.
Page 20
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual The IEC 61850 standard provides: Standardized information models for all kinds of protection relays, controllers, circuit-breakers, transformers, and so on. Information exchange methods to access the information models' data: report sequences-of-events, log historical data, control devices, sampled value distribution, fast peer-to-peer process data exchange, and so on.
Connect the fibre-optic SPA bus cable between IED and SPA-ZC 402. Connect the LAN cable to the LAN connector of SPA-ZC 402. The other end of the cable is connected to the IEC 61850-8 station bus through the Ethernet switch.
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 5.3.2. Installing Communication Engineering Tool for SPA-ZC 40x 1. Uninstall the previous version. 2. Close all the open programs and insert the Communication Engineering Tool (CET) for SPA-ZC 40x installation CD to the CD-ROM drive of your PC.
Detailed instructions for upgrading the software are provided when the upgrade is available. 5.4. Installing Connectivity Packages 1. Close all the open programs and insert the SPA-ZC 402 configuration CD to the CD-ROM drive of your PC. The Connectivity Packages can be downloaded on the ABB web site http://www.abb.com/substationautomation.
Only one version of each Connectivity Package can be enabled at a time. 1. Double-click the icon on the computer's desktop to start the Connectivity Package Manager. 2. Select the corresponding Connectivity Package to enable it for SPA-ZC 402. 3. Click OK to apply the selection, see Fig. 5.4.1.-1.
Communication Engineering Tool (CET) for SPA-ZC 40x. 5.5.1. Changing computer's IP address To connect SPA-ZC 402, the used computer and SPA-ZC 402 must use the same address space. To change the computer's IP address space to be the same as in SPA-ZC 402:...
You must have system administration rights to perform the task. A060241 Fig. 5.5.1.-1 Changing IP address 5.5.2. Checking connection to SPA-ZC 402 Check the connection to SPA-ZC 402 by using the ping command: 1. Open the Run dialog. 2. Type cmd to the Open box, see Fig. 5.5.2.-1.
Page 27
4. Type ping 192.168.2.10, see Fig. 5.5.2.-2. Fig. 5.5.2.-2 Pinging SPA-ZC 402 SPA-ZC 402responds to the ping command if the computer and SPA-ZC 402 are on the same network. 5. If SPA-ZC 402 responds with the IP address, the connection is established...
6.1. Overview of engineering The engineering and maintenance of SPA-ZC 402 is done by using CET for SPA-ZC 40x functions or by importing the existing SPA-ZC 40x CID file. The device's communication structure is described in the Project Explorer dialog. The structure is built by using device objects.
Fig. 6.2.-2 Creating a new project 6.3. Restarting Use this function to restart the SPA-ZC 402 at runtime. 1. Select IED and Tools > Restart SPAZC40x to open the restart panel, see Fig. 6.3.-1 2. Click Reset. The results are reported to the UI text box.
Fig. 6.4.-1 shows an example of the object tree when it has been built. In the example tree you can see the SPA-ZC 402 object and its child objects as devices and data objects. Indentation is used to indicate the parent-child relationship...
Page 32
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040137B Fig. 6.4.-1 Example view of the SPA-ZC 40x Communication Engineering Tool Add objects to the object tree in the communication structure by right-clicking the object to which you want to add a child object.
3. Select New > IEC 61850 > SPAZC40x_v2x, see Fig. 6.4.1.-1. Normally, the SPAZC40x_v2x template from the menu is used. Only if the connected SPA-ZC 402 is an older version 1.1.1, you have to select its own IED template SPAZC40x_v1x from the menu. This is illustrated in the following figure.
Page 34
Adding a new Logical Device object (for example REX 521, see Fig. 6.4.2.-1) is possible only after you have installed Connectivity Packages to your computer. The IED's data model behind SPA-ZC 402 is described in the logical device LD1. For more information about installing Connectivity Packages, refer to Section 5.4.
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual When the actual IEC 61850 data model is created, the logical device name has two parts: Device Object name Logical Device name For example, REF543_F1LD0.
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040026B Fig. 6.4.3.-1 Project Explorer dialog in the Communication Engineering Tool window 6.5. Using Dataset Editor The dataset groups selected data so that a client can access it easily with a single read operation.
Page 37
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual groups, and functional constraint defines the data attributes. This is MMS protocol's naming feature, which is the basic part of naming and protocol definition in the IEC 61850 standard.
6.6. Configuring by using imported CID file If you have to configure several SPA-ZC 402 with the similar IEC 61850 data object model, it is possible to import a previously generated CID file and change the communication addresses, typically by changing the IP address.
SPA Communication parameters SPA Address SPA-ZC 402 needs also an IED SPA address to access the SPA data. Every logical device has SPA Communication Parameters Object properties except LD0, which describes the SPA-ZC 402. The SPA address object property has to be the same as the configured SPA unit number in IED.
Page 40
IED. IED gets the time from external source. Event poll If the parameter is disabled, SPA-ZC 402 does not poll events from IED and the IEC 61850 events are based on a continuous data poll. This feature could be used in systems where, for example the other REF 543 port is already used for the SPA communication.
Fig. 6.7.1.-1 SPA Communication Parameters Locally, SPA-ZC 402 uses UTC (Coordinated Universal Time) time, which is received from the SNTP time synchronization by default. This time format does not use Daylight Saving Time. If you want that the IED and SPA communication uses this time format, the IEC 61850 client has to be programmed to write the minute offset of the UTC time to the LD0.LLN0.
Page 42
1. Select the IEC 61850 Device object and right-click to select the CID Export. 2. If you download configuration to SPA-ZC 402 the first time, change the IP address from default address (192.168.2.10) to new IP address according to the planned network structure.
If a new functionality is added to the IED application, the new IED application (AR file) import is needed. In this case, there are two options: Communication Engineering Tool (CET) for SPA-ZC 402 asks either the old SPA-ZC 402 application is overwritten or only the new functionality is added.
Page 44
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040131B Fig. 6.9.-1 LN wizard 5. Select the new logical node in the project tree. 6. Right-click the logical node and select DO Wizard to start the DO Wizard, see Fig.
Page 45
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040132B Fig. 6.9.-2 DO Wizard 10.Start with the mandatory data objects and then add the process data. Mandatory data objects are Mod, Beh, Health and NamPlt.
Page 46
The SPA point data is written to the sAddr in the CID file for the selected data object. SPA-ZC 402 uses this field to poll data and events from the IED. In order to get automatic updating of the process objects, you should add those data objects of interest to the dataset group.
The default value for Integrity Period is 0 ms. If this attribute has a value > 0 ms, SPA-ZC 402 sends a report with all data listed in a linked data set with this period. By default, this feature is not enabled, because it generates an unnecessary load to the server and network.
Page 48
SPA to IEC 61850 Gateway Installation and Commissioning Manual By default, this attribute is empty and SPA-ZC 402 uses it for RCB MMS address. If this string is left empty, a default report control block MMS path name is used.
Page 49
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A040134B Fig. 6.10.-2 Report Control Block Buffered reporting needs mandatory Report Client definitions. Report Client definitions link a certain RCB to a certain client. The client can import the CID file to check which RCB instance it has to use.
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 6.11. Scales To create a scale: 1. If a Scales object does not exist in the object tree, add the object by right-clicking the project and selecting New >...
Page 51
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual A060132 Fig. 6.11.-2 Configuring properties 5. Create reference to scale at DO level in object tree, see Fig. 6.11.-3...
A relay with compatible MEDREC16 function block notifies SPA-ZC 402 when it has new recordings ready. SPA-ZC 402 reads the actual data from the relay as a background process and stores the data as COMTRADE files in its own file system...
Page 53
When the IEC 61850 client has been notified of the incoming record, the client should read the COMTRADE files from SPA-ZC 402 by using FTP or IEC 61850 File Transfer connection. The client must remove the files after successful reading to maintain free space for forthcoming records.
You can see how the configuration process is progressing from the diagnostic LEDs. When the SPA-ZC 402 configuration is completed, the green LED is on. If SPA-ZC 402 is online with the IEC 61850 client, you can check the general configuration status of SPA-ZC 402 from the data model LD0.LLN0.Health.stVal: 1.
If the configuration is completed successfully, you can check the resettable diagnostic counters through the IEC 61850 data model. SPA-ZC 402 Diagnostic counters are part of the LD0.CDGGIO1 logical node. The data object type is ABB-specific extension in IEC 61850 data model and contains the counters as data attributes.
Page 57
The q attribute reflects the status of data. If the data is properly updated, the data object's quality value is GOOD. If this is not the case, configurations between SPA-ZC 402 and IED are not identical. If all the data objects have INVALID quality, the SPA communication is not...
See fibre-optic guides: SPA-ZF Optical glass fibres, multimode graded index type Plastic-core fibre-optic cables, features and instructions for mounting For more information, see Section 1.4. Product documentation. Diagnostic LEDs SPA-ZC 402 common diagnostic LEDs Power Diagnostic Green Yellow LAN diagnostic LEDs...
Fig. 8.1.-1 Dimensions of the SPA-ZC 402 module Table 8.1.-1 Dimensions and weight Type Dimensions [mm] Weight [g] SPA-ZC 402 190 x 115 x 35 8.2. Test and conditions SPA-ZC 402 fulfills IEC 61850-3 Communication networks and systems in substations.
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual General requirements Table 8.2.-1 Environmental test and conditions Recommended service temperature range -10...+55˚C (continuous) Limited temperature range (short-term) -40...+85˚C Transport and storage temperature range -40...+70˚C according to the IEC 60068-2-48...
Page 62
According to the IEC 60255-21-1, class I Shock and bump test According to the IEC 60255-21-2, class I Table 8.2.-4 Auxiliary power supplies Type SPA-ZC 402 xxxA SPA-ZC 402 xxxC Input voltage AC 110/120/220/240 V Input voltage DC 110/125/220 V...
Installation and Commissioning Manual Maintenance and service If the SPA-ZC 402 module or a part of it is found to be faulty, the normal service operation is to replace the entire module. For more details, refer to Section 13. Ordering information.
The following IED-specific settings have to be checked when setting up REF 541/3/5, REM 543/5 or RET 541/3/5: SPA baud rate and SPA slave number in IED Baud rate and slave number have to be according to the SPA-ZC 402 configuration in X3.2/Communication 2. 9.3.
Installation and Commissioning Manual Select Help > About to view the version information. SPA-ZC 402 version information The version information can be read from the device's label. If the device is updated afterwards, use CET's IP query to get the correct version information from the device memory.
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Troubleshooting Communication to SPA-ZC 40x is not working If communication problems occur, check the firewall configurations. Table 10.-1 shows the ports that have to be open in firewall.
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Technical reference This chapter defines the compliance to IEC 61850 in terms of service, modeling, engineering interfaces and also exceptions and local adaptations. The information gives you a detailed explanation of the IEC 61850 capabilities of a product.
. It is also possible to export the information in MICS to a CID file. The CID file can be used in the system tool, see Safety information. Some of the data cannot be retrieved from the IED, but it is the default value in the SPA-ZC 402. 11.2.1.
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.1.2. Analogue value Table 11.2.1.2.-1 Analogue value AnalogueValue Type Definition SPA-ZC 402/ Attribute Name AttributeType Value/ Value Range M/O/C Comments INT32 integer value...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.2. Double point status (DPS) The table 11.2.2.2.-1 defines the common data class of double point status. Table 11.2.2.2.-1 Double point status (DPS)
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual INS class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments Substitution subEna BOOLEAN PICS_SUBST Not Supported subVal CtxInt PICS_SUBST...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual ACT class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments Different variants of the type exist based on the connectivity package short address information (sAddr).
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual ACD class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255 cdcName VISIBLE AC_DLNDA_M Not Supported...
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual MV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments range ENUMERATED dchg normal | high | Supported low | high-high | low-low | …...
Page 81
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.9.-1 Complex measured value (CMV) CMV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.10. Table 11.2.2.10.-1 defines the common data class of WYE. Table 11.2.2.10.-1 WYE SAV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.11.-1 Delta (DEL) SAV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual SAV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments A | B | C | … phsRef ENUMERATED...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual HMV class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255 cdcName VISIBLE AC_DLNDA_M Not Supported...
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual HWYE class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments resHar ARRAY[0.. dchg, dupd Not Supported numHar] OF Vector...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual HDEL class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments phsBCHar ARRAY[0.. dchg, dupd Not Supported numHar] OF Vector phsCAHar ARRAY[0..
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual SPC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments stVal BOOLEAN dchg FALSE | TRUE AC_ST Supported Quality...
Page 89
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.17.-1 Controllable double point (DPC) SPC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (see IEC 61850-7-2)
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual Different variants of the type exist based on the connectivity package short address information (sAddr). Underlined information indicates the basic type. 11.2.2.18. Controllable integer status (INC) Table 11.2.2.18.-1 defines the common data class of controllable integer status.
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual BSC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments subID VISIBLE PICS_SUBST Not Supported STRING64 Configuration, Description and Extension...
Page 93
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.20.-1 Integer controlled step position information (ISC) ISC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName...
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual Status-only is supported for the ctlModel. 11.2.2.21. Controllable analogue set point information (APC) Table 11.2.2.21.-1 defines the common data class of controllable analogue set point information.
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.2.2.22.-1 Single point setting (SPG) APC class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments DataName Inherited from Data Class (refer to IEC 61850-7-2)
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual 11.2.2.24. Analogue setting (ASG) Table 11.2.2.24.-1 defines the common data class of analogue setting. Table 11.2.2.24.-1 Analogue setting (ASG) ASG class Value/ Value...
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual ASG class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments setParF FLOAT32 SG SE AC_NSG_O Not Supported setCharact ENUMERATED...
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual ASG class Value/ Value SPA-ZC 402/ Attribute Name Attribute Type TrgOp M/O/C range Comments cdcNs VISIBLE AC_DLNDA_M Not Supported STRING255 cdcName VISIBLE AC_DLNDA_M Not Supported...
SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 1MRS755380 SPA to IEC 61850 Gateway Installation and Commissioning Manual Table 11.5.1.-1 A-profile support SPA-ZC 402/ Client Server Comments Client/Server A- Supported Profile GOOSE/GSE Not Supported Management A- Profile GSSE A-Profile Not Supported...
Page 103
1MRS755380 SPA/ Ethernet Adapter SPA-ZC 402 SPA-ZC 402 SPA to IEC 61850 Gateway Installation and Commissioning Manual Subscriber Publisher SPA-ZC 402/Comments GSENotSupported Not Supported GOOSE Control Block (GoCB) Not Supported Must be m if support is declared within ACSI basic conformance.
SPA-ZC 402 configuration CD Engineering tool, Communication Engineering Tool (CET) for SPA-ZC 40x Order at least one SPA-ZC 402 configuration CD with your delivery to get the Communication Engineering Tool. The SPA-ZC 402 package does not include the configuration CD by default.
Furthermore, they can be used as IED internal identification for the attribute. Snap-in Connector type for plastic fibre cable Data communication protocol developed by ABB...
Supervision, control and data acquisition Substation configuration description language (defined by IEC 61850) SNTP Simple Network Time Protocol Data communication protocol developed by ABB Structured query language Straight-tip; a connector type for fibre optic cable Shielded twisted pair Universal time clock...