Definable Content List Of Programmable Output Ports 1-5 - Smartgen HGM4020DC User Manual

Genset controller
Table of Contents

Advertisement

No.
Items
Mains Abnormal And Pile Low Volt Start
1
Start Set
2
Stop Condition
3
Pile Volt Upper Limit
4
Pile Volt Lower Limit
5
Charge Finish Time
6
Under Current
7
Under Current Delay
Minimum Charge
8
Time
Mains Abnormal And Room Temp. High Start
1
Start Set
Room Temp. Upper
2
Limit
Room Temp. Lower
3
Limit
NOTES:
1) When parameter configuration is operated via PC software, there is no need to input password if default password
(0318) isn't changed. On the contrary, if default password has been changed or it is the first time to set parameters via
PC, password is needed to input in the password interface.
2) After the correct password is entered, before LCD backlit gets dark, parameter setting interface can be entered directly
by inputting parameter serial at secondary entering the password interface.

7.2 DEFINABLE CONTENT LIST OF PROGRAMMABLE OUTPUT PORTS 1-5

Table 11 – Definable Contents of Programmable Outputs 1~5
No.
Items
0
Not Used
1
Common Alarm
2
Common ELE Trip
3
Common Shutdown
4
Common Warn Alarm
5
Audible Alarm
6
Energized to Stop
7
Idle Control
HGM4020DC Genset Controller
HGM4020DC GENSET CONTROLLER USER MANUAL
Range
Default
(0-30000)min
30
(0-1)
1
(0-3)
0
(0-100.0)V
58.0
(0-100.0)V
45.0
(1-6000)min
720
(1-100)%
15
(10-3600)s
30
(0-360)min
30
(0-1)
1
(15-55)º C
28
(15-55)º C
22
Output port don't output when it is chosen.
Include all shutdown alarms, trip and stop alarms and warning alarms.
When there is warning alarm only, it is not self-locked; when a shutdown
alarm occurs, it is self-locked until the alarm is reset.
Output when a common trip shutdown alarm occurs.
Output when a shutdown alarm occurs.
Output when a common warning alarm occurs.
When warning, trip shutdown and shutdown alarms appear, audible
alarm output is fixed for 300s, during which if any button on the panel is
pressed, or "alarm mute" input is active, or any keys on the panel is
active, the alarms shall be removed.
Applicable for genset with stop electromagnet; it shall pull in when stop
idle speed running ends and disconnect when the set ETS delay is over.
Applicable for genset with idle speed; it shall pull in when genset starts
and disconnect when warming up is initiated; it shall pull in during stop
idle speed process and disconnect when genset stops completely.
Version 1.0
Description
Time(Minute)
Duration time
0: Not Start; 1: Start
0: Pile Volt High and Current Low
1: Pile Volt High
2: Current Low
3: Pile Volt High or Current Low
It is battery voltage when battery is
completely charged.
It is battery pack under voltage limit. If
voltage of battery falls below the setting
value, genset will be started.
It is the maximum time to charge for once.
When load current of switch power is lower
than the set value, and battery voltage is
higher than the upper limit value as well,
genset will be allowed to stop.
When genset is normal running, if load
current is below pre-set lower limit value,
this delay will be started.
When battery charging time exceeds the set
value, and if temperature of machine room is
high, air conditioner will be started.
0: Not Start; 1: Start;
Genset will start up if machine room is
higher than this value.
After genset starts up because of the high
temp. of machine room, if room temp. falls
below the set value, genset will stop.
Function Description
2019-04-10
Page 23 of 31