DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER CONTENTS AND RANGE

No
Items
1
Mains Normal Delay
2
Mains Abnormal Delay
3
Mains Under Volt
4
Mains Over Volt
5
Transfer Rest Delay
6
Start Delay
7
Stop Delay
8
Start Attempts
9
Preheat Time
10
Cranking Time
11
Crank Rest Time
12
Safety On Delay
13
Start Idle Time
14
Warming Up Time
15
Cooling Time
16
Stop Idle
17
ETS Solenoid Hold
18
Fail to Stop Delay
HGM400N Series Genset Controller
HGM400N Series Genset Controller User Manual
Range
Default
(0-3600)s
10
(0-3600)s
5
(30-620)V
184
(30-620)V
276
(0-99.9)s
1.0
(0-3600)s
1
(0-3600)s
1
(1-10)times
3
(0-300)s
0
(3-60)s
8
(3-60)s
10
(1-60)s
10
(0-3600)s
0
(0-3600)s
10
(3-3600)s
10
(0-3600)s
0
(0-120)s
20
(0-120)s
0
2017-04-21
Description
The time from mains abnormal to normal or
from normal to abnormal; suitable for ATS
(automatic transfer switch).
When mains voltage has fallen below the set
value, Mains Under Voltage is active. When set
the value as 30V, the controller does not detect
under voltage signal. Back lash: 10V
When mains voltage has exceeded the set
value, Mains Over Voltage is active. When set
the value as 620V, the controller does not
detect over voltage signal. Back lash: 10V
Interval time from mains switch off to generator
switch on; or from generator switch off to mains
switch on.
Time from mains abnormal or remote start
signal is active to start genset.
Time from mains normal or remote start signal
is deactivated to genset stop.
Maximum crank times of crank attempts. When
reach this number, controller will send start
failure signal.
Power-on time of heater plug before starter is
powered up.
Power-on time of starter
The waiting time before second power up when
engine start fail.
Alarms for low oil pressure, high temperature,
under speed, under frequency/voltage, charge
alt failure are inactive.
Idle running time of genset when starting.
Warming time between genset switch on and
high speed running.
Radiating time before genset stop, after it
unloads.
Idle running time when genset stop.
Stop electromagnet's power on time when
genset is stopping.
Time between ending of genset idle delay and
stopped when "ETS time" is set as 0;
Time between ending of ETS hold delay and
Version 1.2
Page 18 of 36