7 DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER SETTING CONTENTS AND RANGE

No.
Items
P00
Mains Normal Delay
Mains
Abnormal
P01
Delay
Mains Under Volt
P02
Threshold
Mains
Over
P03
Threshold
P04
Mains Options
P05
Start Delay
P06
Stop Delay
P07
Crank Attempts
P08
Preheat Time
P09
Cranking Time
P10
Crank Rest Time
P11
Safety On Delay
P12
Start Idle Delay
P13
Warming Up Time
P14
Cooling Time
P15
Stop Idle Delay
P16
ETS Solenoid Hold
P17
Wait for Stop
MGC300 Series Genset Controller User Manual
Table 7 Parameter Setting Contents and Range
Range
(0~3600)s
(0~3600)s
(30~6000)V
Volt
(30~6000)V
(0~1)
(0~3600)s
(0~3600)s
(1~10) times
(0~300)s
(3~60)s
(3~60)s
(1~60)s
(0~3600)s
(0~3600)s
(3~3600)s
(0~3600)s
(0~120)s
(0~120)s
Default
10
Confirm time duration for Mains voltage
from abnormal to normal or from normal to
5
abnormal to be used for ATS transfer.
If the voltage sample is lower than it, mains
under voltage is considered; When it is set
184
30V, under voltage signal shall not be
detected; return difference is 10V.
If the voltage sample is higher than it,
mains over voltage is considered; When it
276
is set 6000V, over voltage signal shall not
be detected; return difference is 10V.
0
0: AMF
1: Display Only
Time duration from mains abnormal or
1
remote start signal is active to genset
startup.
Time duration from mains normal or remote
1
start signal is deactivated to genset stop.
It is maximum crank attempts when engine
3
fails to start. When it is reached, controller
shall send out crank failure signal.
Preheating
0
before starter is powered on.
8
Time for starter to be energized every time.
The waiting time before second power up
10
when engine start fails.
Alarms for low oil pressure, temp. high,
10
under speed, under frequency and under
voltage, charging failure are deactivated.
0
Time for genset idle running at starting.
Warming-up time before breaker close after
10
high speed running for genset.
Radiating time before genset stop after
10
genset is unloaded.
0
Time for genset idle running at stopping;
The time for stop electromagnet to be
20
energized before genset stop.
Time from idle delay to complete stop when
0
ETS stop output is set to 0s; when the
Description
plug
pre-energization
Page 16 of 26